2018-08-06 14:49:2708/06/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WASHING MACHINE VALVES MUST BE ACCESSIBLE FOR
 SHUTTING OFF WITHOUT MOVING UNITS, PLEASE ADD TO PLAN
 KEY NET AS AN ITEM NUMBER. 2017 FBC SEC R2903.9.3
 FIXTURE VALVES AND ACCESS. ACCESSIBLE, SIGNIFIES ACCESS
 THAT REQUIRES THE REMOVAL OF AN ACCESS PANEL OR SIMILAR
 REMOVABLE OBSTRUCTION.
 2. SHOW HAMMER ARRESTORS ON ISOMETRIC. WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW