2018-07-17 11:27:37 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| 2. NOTE 1 DETAILING AFCI PROTECTION IS NOT CODE |
| COMPLIANT. PER CODE, ALL BRANCH CIRCUITS THAT SUPPLY |
| 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS |
| INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS, |
| LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, |
| SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS, |
| LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI |
| PROTECTED. SOME AREAS REQUIRE GFCI AND AFCI PROTECTION. |
| PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902.16 |
| 3. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| 210.8(D); FBC RE E3902.10 |
| 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| FBC EC C405.1, R404.1 |
| 5. ROOM 107 BATHROOM DOES NOT SHOW THE REQUIRED GFCI |
| PROTECTED RECEPTACLE OUTLET WITHIN 3 FEET OF THE BASIN. |
| PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE |
| E3703.4, E3901.6 |
| 6. SHEET M-2 STATES THAT CU-3 REQUIRES A MINIMUM |
| CIRCUIT AMPACITY OF 32 AMPS. PLAN SHOWS #10 WIRE |
| FEEDING THIS UNIT. THE #10 ROMEX IS ONLY RATED FOR 30 |
| AMPS. PROVIDE CORRECTION. NEC 334.80; FBC RE E3705.4.4 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |