2018-08-02 18:20:0008/02/2018 1ST GAS REVIEW **DENIED** WITH COMMENTS
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT TWO COPIES OF MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT(TANKLESS) TO VERIFY COMPLIANCE WITH 2017 FBC
 FUEL GAS SEC.305.1 OR 2017 FBC FUEL GAS RES. SEC.
 G2408.1.
 2. PLEASE SHOW THE LOCATION OF THE TANKLESS WATER
 HEATER AND THE LOCATION AND DISTANCE OF ANY OPERABLE
 DOORS OR WINDOWS IN RELATION TO THE WATER HEATER. THE
 LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 3. SUBMIT TWO COPIES MANUFACTURER'S SPECIFICATIONS FOR
 THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC
 FUEL GAS RES. SEC. G2421.1.
 4. A ELECTRICAL OUT MAY BE REQUIRED FOR SOURCE OF
 IGNITION, WPB AMENDMENTS TO THE FBC SEC 105.1
 5. A SEPARATE GAS PERMIT SHALL BE REQUIRED, FBC WPB A
 107.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  