Plan Review Notes
Plan Review Notes For Permit 18061057
Permit Number 18061057
Review Stop B
Sequence Number 1
Notes
Date Text
2018-07-20 12:38:51****CORRECTIONS****
 W.P.B. PERMIT: 18061057
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 107.3.5.3]ADD THE CONSTRUCTION TYPE TO PROJECT
 DATA.
  
 2. [FBC ENERGY R401.2]THE ENERGY CALCULATIONS PROVIDED
 DIDN'T ACCOUNT FOR FLOOR INSULATION AT UNDER FLOOR
 CRAWL SPACE. PLEASE UPDATE AND SUPPLY R-VALUE. PAGE 2
 OF 4 CHANGE FLOOR TYPE FROM SLAB ON GRADE, AND CHECK
 ATTIC IT SAYS BLOWN IN INSULATION.
 [FBC R302.10]PROVIDE CUT SHEET FOR ICYNENE(ICC-ES
 REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH
 THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD
 INDEX AND SMOKE DEVELOPED INDEX.
  
 3. [FBC R107.2.5]PROVIDE DEMOLITION NOTES TO REMOVE THE
 EXISTING FOUNDATION AND OTHER STRUCTURAL ELEMENTS.
 PROVIDE SHORING/JACKING NOTES IF APPLICABLE TO EXPLAIN
 HOW TO THE EXISTING STRUCTURE WILL BE SUPPORTED WHILE
 THE NEW FOUNDATION IS BEING CONSTRUCTED.
 SEPARATE PERMIT FOR DEMO WILL BE NEEDED.
  
 [FBC 107.3.4.1]DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL FOR
 REVIEW, AND THEN FORWARED TO THE BUILDING
 OFFICIAL INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN. THE DEFERRED SUBMITTAL ITEMS
 SHALL NOT BE INSTALLED UNTIL THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING OFFICIAL.
  
 4. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR
 WINDOWS, WINDOW MULL, DOORS, TRANSOMS, SLIDERS AND
 SOLAR TUBES, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFFERED.
  
 5. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR
 ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFFERED.
  
 6. [FBC R408.4]PROVIDE ACCESS TO THE UNDER FLOOR SPACE
 18X24 MINIMUM.
  
 7. [FBC 107.3.5.3]PROVIDE DETAIL OF HOW UNDER FLOOR
 VENTS WORK WITH THE FOUNDATION.
  
 08. [FBC R408.2]SUPPLY CALCULATION TO SHOW HOW MUCH
 VENTILATION IS NEEDED UNDER FLOOR SPACE AND HOW MUCH IS
 SUPPLIED.
  
 09. [FBC R507]WHAT CONNECTORS ARE BEING USED TO CONNECT
 THE REAR WOOD DECK TO THE EXISTING STRUCTURE?
  
 10. [FBC 107.3.5.3]UPDATE CODE REFERENCE TO CURRENT
 CODE ON SHEET S-200 WIND LOAD SCHEDULE.
  
 11. [FBC 107.3.5.3]ADJUST DETAILS ON S-300 TO REFLECT
 THAT THE STRUCTURE IS CURRENTLY STUCCO(NOT WOOD
 SIDING). SHOW STUCCO DETAILS AT FOUNDATION AND OTHER
 AREAS OF ALTERATION.
  
 12. [FBC R302.11]VERIFY AND UPDATE FIREBLOCKING IF
 APPLICABLE TO BALLOON FRAMING. IS FIREBLOCKING BEING
 PROVIDED BETWEEN FLOORS (SHEET 1/A200)?
  
 13. [FBC 107.3.5.3]ARE OUTLOOKERS GOING AT SHEAR WALL
 AND OTHER AREAS? PLEASE SHOW HOW THESE WILL LOOK ON THE
 ELEVATIONS.
  
 14. [FBC R3-1.2(6)]PROVIDE WIND DIAGRAM THAT MATCHES
 THE ROOF CONDITION OF THIS HOUSE(FLAT ROOF WITH
 PARAPET).
  
 15. [FBC R803.2.3.1]UPDATE SHEATHING FASTENING ON S-300
 & S-301.
 SHEATHING NAILS TO BE RING SHANK RSRS01(2 3/8 X 0.113)
  
 16. [FBC R903.4]ROOF DRAINAGE AND SCUPPERS. PROVIDE
 ROOF DRAINAGE CALCULATION AND SHOE SCUPPER LOCATIONS
 AND SIZING. IF SCUPPERS ARE TO BE ON EAST SIDE PARAPET,
 SHOW HOW THE WATER WILL BE MANAGED ON THE SITE DRAINAGE
 PLAN.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  