Plan Review Notes For Permit 18060978 |
Permit Number |
18060978 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-28 09:06:34 | 1. ENSURE HYDRAULIC CALCULATIONS MATCH AREA INDICATED | | ON THE PLANS. | | 2. ENSURE SIDEWALL SPRAY PATTERNS ARE NOT OBSTRUCTED BY | | CEILING FAN INSTALLATION IN MAIN LIVING AREAS. | | 3. REVIEW HYDRAULIC CALCULATIONS INFORMATION TO ENSURE | | ADEQUATE PRESSURE REQUIREMENTS. | | 4. PROVIDE DATA SHEET FOR TYCO SPRINKLER HEAD 3331 | | 5. REVIEW UNITS B2-A ON ALL FLOORS AS IT APPEARS TO BE | | LACKING COVERAGE UNDER SOFFIT. TO BE VERIFIED IN THE | | FIELD. | | | | S. THOMAS | | 561-8044728 |
|