Plan Review Notes
Plan Review Notes For Permit 18060978
Permit Number 18060978
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-06-28 09:06:341. ENSURE HYDRAULIC CALCULATIONS MATCH AREA INDICATED
 ON THE PLANS.
 2. ENSURE SIDEWALL SPRAY PATTERNS ARE NOT OBSTRUCTED BY
 CEILING FAN INSTALLATION IN MAIN LIVING AREAS.
 3. REVIEW HYDRAULIC CALCULATIONS INFORMATION TO ENSURE
 ADEQUATE PRESSURE REQUIREMENTS.
 4. PROVIDE DATA SHEET FOR TYCO SPRINKLER HEAD 3331
 5. REVIEW UNITS B2-A ON ALL FLOORS AS IT APPEARS TO BE
 LACKING COVERAGE UNDER SOFFIT. TO BE VERIFIED IN THE
 FIELD.
  
 S. THOMAS
 561-8044728