2018-06-29 18:53:17RESIDENTIAL (R3) MECHANICAL REVISION REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014).
  
  
 1- BEDROOM/DEN TRANSFER DUCT SIZE SPECIFIED DOESN'T
 COMPLY WITH THE BALANCED RETURN AIR SEC. M1602.4
 FBC-RESIDENTIAL. THERE ARE TWO SUPPLY DUCTS SHOWN FOR
 THIS ROOM. PLAN SHOW A 9" TRANSFER DUCT. NEED AT LEAST
 A 10" TRANSFER DUCT. REVISE AS REQUIRED.
  
  