Plan Review Notes
Plan Review Notes For Permit 18060927
Permit Number 18060927
Review Stop G
Sequence Number 3
Notes
Date Text
2018-07-28 07:59:341) THIS RESUBMITTAL IS A CONVOLUTED MESS AND IN
 DISSARAY. THERE ARE TWO DIFFERENT GAS DRWAINGS,
 MULTIPLE COPIES OF ONE GAS DRAWING,ONLY ONE COPY OF
 ANOTHER, MULTIPLE COPIES OF RINNAI SPECS AND REGULATOR
 SPECS. NOTHING IS IN ORDER. THERE ARE MULTIPLE COPIES
 OF PERMIT APPLICATIONS, ETC. SOMEONE FROM THE
 CONTRACTOR'S OFFICE SHALL COME TO THE BUILDING DIVISION
 AND REMOVE ALL THE OLD PLANS AND ARRANGE THESE
 DOCUMENTS INTO TWO COMPLETE SETS OF PLANS FOR REVIEW.
 WPB AMEND. TO FBC SEC. 107.2.1, 107.1. I WILL NOT DO A
 REVIEW UNTIL THIS IS DONE.
 2) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 FOR THE LOW PRESSURE SYSTEM USED TO SIZE THE GAS SYSTEM
 OR PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH
 SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD
 THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER
 TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND
 TABLES 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3.
 3) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS
 SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
 4) ) SUBMIT LEGIBLE COPIES OF THE MANUFACTURER?S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. IDENTIFY ON THE SPECIFICATION SHEETS
 WHICH MODEL REGULATOR IS BEING INSTALLED AND THE
 ORIFICE SIZE TO ENSURE THE REGULATOR CAN ACCOMMODATE
 THE BTU LOAD THROUGH THE REGULATOR.2017 FGC SEC.410.1,
 2017 FBC-RES. SEC. G2421.1.
 5) THE ABANDONED POOL HEATER AND FIREPLACE LINES SHALL
 BE EQUIPPED WITH A SHUTOFF VALVE, PRESSURE REGULATOR, A
 NIPPLE AND A CAP. 2017 FBC-FUEL GAS SEC.404.15. THIS IS
 REQUIRED TO ENSURE THE GAS SYSTEM IS LEFT IN A SAFE
 CONDITION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  