2018-07-28 07:59:34 | 1) THIS RESUBMITTAL IS A CONVOLUTED MESS AND IN |
| DISSARAY. THERE ARE TWO DIFFERENT GAS DRWAINGS, |
| MULTIPLE COPIES OF ONE GAS DRAWING,ONLY ONE COPY OF |
| ANOTHER, MULTIPLE COPIES OF RINNAI SPECS AND REGULATOR |
| SPECS. NOTHING IS IN ORDER. THERE ARE MULTIPLE COPIES |
| OF PERMIT APPLICATIONS, ETC. SOMEONE FROM THE |
| CONTRACTOR'S OFFICE SHALL COME TO THE BUILDING DIVISION |
| AND REMOVE ALL THE OLD PLANS AND ARRANGE THESE |
| DOCUMENTS INTO TWO COMPLETE SETS OF PLANS FOR REVIEW. |
| WPB AMEND. TO FBC SEC. 107.2.1, 107.1. I WILL NOT DO A |
| REVIEW UNTIL THIS IS DONE. |
| 2) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| FOR THE LOW PRESSURE SYSTEM USED TO SIZE THE GAS SYSTEM |
| OR PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH |
| SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD |
| THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER |
| TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND |
| TABLES 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. |
| G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3. |
| 3) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS |
| SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4. |
| 4) ) SUBMIT LEGIBLE COPIES OF THE MANUFACTURER?S |
| SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. IDENTIFY ON THE SPECIFICATION SHEETS |
| WHICH MODEL REGULATOR IS BEING INSTALLED AND THE |
| ORIFICE SIZE TO ENSURE THE REGULATOR CAN ACCOMMODATE |
| THE BTU LOAD THROUGH THE REGULATOR.2017 FGC SEC.410.1, |
| 2017 FBC-RES. SEC. G2421.1. |
| 5) THE ABANDONED POOL HEATER AND FIREPLACE LINES SHALL |
| BE EQUIPPED WITH A SHUTOFF VALVE, PRESSURE REGULATOR, A |
| NIPPLE AND A CAP. 2017 FBC-FUEL GAS SEC.404.15. THIS IS |
| REQUIRED TO ENSURE THE GAS SYSTEM IS LEFT IN A SAFE |
| CONDITION. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |
| |
| |
| |
| |