Plan Review Notes For Permit 18060927 |
Permit Number |
18060927 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-07-19 15:30:57 | 07/19/2018 2ND GAS REVIEW**DENIED** | | | | 1) PLAN SUBMITTED SHALL NOT BE IN PENCIL AND SHALL BE | | OF PERMANENT SOURCE.107.3.5MINIMUM PLAN REVIEW CRITERIA | | FOR BUILDINGS | | | | 2) EVEN WITH THE POOL HEATER AND FIRE PLACING BEING | | CAPPED THE GAS SUPPLY TO THEM COULD AT SOME TIME BE | | RECONNECTED AND SHALL BE INCLUDED ON YOUR PLAN AND SHOW | | AS A BTU LOAD. FBC FUEL AND GAS 401.8, 402.1 | | | | 3) SHOW WHERE EXISTING HEATER IS LOCATED ON FLOOR PLAN. | | FBC 107.2.1 | | | | | | TIM HUNT | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | 561-805-6695 | | [email protected] |
|