Plan Review Notes
Plan Review Notes For Permit 18060927
Permit Number 18060927
Review Stop G
Sequence Number 1
Notes
Date Text
2018-06-29 14:30:1106/29/2018 1ST GAS REVIEW**DENIED**
  
 1) CITY RECORDS SHOW A POOL HEATER INSTALLED UNDER
 PERMIT # 99120567 AND A RANGE AND FIREPLACE INSTALLED
 UNDER PERMIT # 05091464. NOT ALL OF THESE ARE SHOWN ON
 YOUR PLAN. LIST THE BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4
 AND TABLES G2413.4 (1 ) THROUGH G2413.4 (21). . THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. . FGC SECS. 401.4,
 401.8, 402.1, 402.2, 402.3 OR FBCR SECS.G2412.4,
 G2412.8, G2413.1, G2413.2, G2413.3.
  
 2) YOU ARE SHOWING THE SYSTEM AS A 2 PSI SYSTEM BUT DID
 NOT INCLUDE ANY INSTALLATION MANUALS FOR THE PRESSURE
 REGULATORS.SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
  
 3) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS
 REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT
 REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT
 BEING ADDED TO THE EXISTING HOT WATER SYSTEM? INDICATE
 ON THE APPLICATION IN THE DESCRIPTION OF WORK.
  
 4) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2.
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER