Plan Review Notes For Permit 18060904 |
Permit Number |
18060904 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-20 15:18:33 | 06/20/2018 1ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH | | COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. ALL BACKFLOW DEVICES MUST BE LEAD FREE. P2906.2.1 | | LEAD CONTENT OF DRINKING WATER PIPE AND FITTINGS. | | | | 2. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS | | ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY | | OF SOUTHERN CALIFORNIA (USC). PLEASE CONTACT DEPARTMENT | | OF PUBLIC UTILITY FIELD CUSTOMER SERVICE AT | | 561-822-2240 FOR DOCUMENTED CONFIRMATION THAT THE | | PROPOSED BACKFLOW PREVENTION DEVICE COMPLIES WITH CITY | | REQUIREMENTS. | | | | THIS BACKFLOW IS NOT A LEAD-FREE DEVICE WHICH IS | | REQUIRED BY THE CITY OF WEST PALM BEACH UTILITY | | DEPARTMENT. YOU CAN REFER TO THEIR CROSS CONNECTION | | MANUAL IN THE CITY WEB SITE HTTP://WPB.ORG/DEPARTMENTS/ | | PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BACKFLOW-CROSS-CONN | | ECTION-CONTROL-MANUAL FOR MORE INFORMATION. THE 975XL | | WATKINS MODEL IS NOT LEAD-FREE AS THE 975XL2 IS SO | | PLEASE RESUBMIT SPECS FOR IT. | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | [email protected] | | 561-805-6720 | | |
|