2018-06-27 16:26:19 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18060878 |
| 6/27/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) CONTRACTOR'S SIGNATURE SHALL BE ON THE PLAN- SECTION |
| 107.2.1 FBC. WPB: ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN. |
| |
| 2) SHOW THE LOCATIONS OF ALL RETURN GRILLS OR TRANSFERS |
| AND PROVIDE DIMENSIONS- SECTION 601.5 AND 601.6 FBC M |
| |
| 3) IDENTIFY ALL ROOMS AND SPACES ON THE PLAN- SECTION |
| 601.5 FBC M, AND SECTION 107.2.1 WPB. |
| |
| 4) PROVIDE A MINIMUM 8" DUCT TO SUPPLY THE 225 CFMS OF |
| AIR TO THE BEDROOM SHOWN TO THE LEFT OF THE BATH- |
| DUCTULATOR AT 0.1" FRICTION LOSS. |
| |
| 5) THE DUCT BOARD SHALL BE R-4.2- TABLE C403.2.9.1 FBC |
| EC. |
| |
| 6) CLARIFY THE LOCATION OF THE DRYER EXHAUST DUCT, AND |
| NOTE THAT IT SHALL NOT BE RUN THROUGH THE PLENUM- |
| SECTION 504.4 FBC M. |
| |
| 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE KITCHEN |
| HOOD AND EXHAUST DUCT. NOTE: MAKEUP AIR MAY BE REQUIRED |
| PER SECTIONS 505.1 & 505.2 FBC M. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |