Plan Review Notes For Permit 18060761 |
Permit Number |
18060761 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-19 15:20:31 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | 1) THERE ARE NO INDICATIONS THAT THE FIRE SUPPRESSION | | SYSTEM IS TIED INTO THE FIRE ALARM. | | | | PER NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE | | PROTECTION OF COMMERCIAL COOKING OPERATIONS, 2014 | | EDITION | | | | 10.6 SYSTEM ANNUNCIATION. | | 10.6.1 UPON ACTIVATION OF AN AUTOMATIC | | FIRE-EXTINGUISHING SYSTEM, | | AN AUDIBLE ALARM OR VISUAL INDICATOR SHALL BE PROVIDED | | TO | | SHOW THAT THE SYSTEM HAS ACTIVATED. | | | | | | 10.6.2 WHERE A FIRE ALARM SIGNALING SYSTEM IS SERVING | | THE OCCUPANCY | | WHERE THE EXTINGUISHING SYSTEM IS LOCATED, THE | | ACTIVATION | | OF THE AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL | | ACTIVATE | | THE FIRE ALARM SIGNALING SYSTEM. | | | | | | PLEASE PROVIDE FOR THE TIE IN AND SUBMITT REVISIONS TO | | ACCURATLEY SHOW ON THE DRAWING. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|