2018-06-27 17:45:34 | 1ST REVIEW FBC-2017 RESIDENTIAL MECHANICAL |
| PERMIT #18060742 |
| 6/27/18 |
| |
| CODES IN EFFECT: |
| |
| FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE AC SYSTEM CHOSEN FOR THE GARAGE IS AN AHRI |
| CERTIFIED HEAT PUMP SYSTEM. IT IS NOT CERTIFIIED, |
| TESTED, OR RATED AS A DEHUMIDIFER. DEHUMIDIFIERS FALL |
| UNDER A SEPARATE CERTIFICATION CATEGORY AND ARE NOT |
| DESIGNED FOR COMFORT CONDITIONING. IF CHOOSING TO USE |
| THIS SYSTEM, PLEASE PROVIDE AC LOAD CALCULATIONS PER |
| SECTION R403.7.1 FBC EC, AND ENERGY CALCULATIONS FOR |
| THE GARAGE PER THE FOLLOWING ENERGY CODE SECTIONS: |
| R502.1, R503.2, R202 , AND R101.2- R101.5.1.2 FBC EC. |
| |
| 2) PROVIDE AN ELECTRICAL PLAN- SECTION 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |