2018-07-09 16:40:07 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC |
| 109.3 (CONTRACT WAS NOT SIGNED AND THEREFORE NOT VALID. |
| THE SIGNATURE OF OWNER WAS ON THE UTILITIES PAPERWORK, |
| SO IT OBVIOUSLY IS ATTAINABLE.) |
| 2. ALL COPIES OF PLAN SHEETS ARE REQUIRED TO HAVE THE |
| SIGNATURE, PRINTED NAME, AND LICENSE NUMBER(IF |
| APPLICABLE) OF THE PERSON RESPONSIBLE FOR THE DESIGN. |
| THIS INCLUDES THE LOAD CALCULATION SHEET AND RISER |
| DIAGRAM. PROVIDE CORRECTION. WPB FBC 107.1, 107.2.1 |
| (SEVERAL SHEETS IN PACKAGE ARE NOT SIGNED BY THE |
| QUALIFIER. IF ANY SHEETS ARE NOT TO BE USED, THEY |
| SHOULD BE REMOVED OR MARKED AS VOID. ALL OTHER SHEETS |
| MUST BEAR THE NAME AND SIGNATURE OF THE QUALIFIER.) |
| 3. RISER DIAGRAM SHOWS THE NEW 200 AMP TRANSFER SWITCH |
| FEEDING THE LOAD CONTROL MODULE. IT SEEMS THAT THIS |
| TRANSFER SWITCH SHOULD FEED A PANEL, WHICH THEN FEEDS |
| THE LOAD CONTROL MODULE TO THE LOADS THAT ARE BEING |
| MANAGED. ALSO, HOW IS THE WHOLE HOUSE ON THE GENERATOR |
| WHEN THERE IS STILL A 100 AMP MAIN THAT IS NOT |
| CONNECTED TO THE GENERATOR? PROVIDE CLARIFICATION |
| AND/OR CORRECTION. SHOW ALL LOADS BEING MANAGED. NEC |
| 215.5; WPB FBC 107.2.1 (RISER DIAGRAM WIRING DOES NOT |
| MATCH THE SPEC SHEET INSTALLATION AS PROVIDED AND DOES |
| NOT MAKE SENSE. PROVIDE CORRECTED RISER DIAGRAM SHOWING |
| ALL PANELS FEED FROM THE TWO TRANSFER SWITCHES AS |
| PREVIOUSLY REQUESTED.) |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |