Plan Review Notes
Plan Review Notes For Permit 18060688
Permit Number 18060688
Review Stop E
Sequence Number 1
Notes
Date Text
2018-06-20 13:53:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC
 109.3
 2. ALL COPIES OF PLAN SHEETS ARE REQUIRED TO HAVE THE
 SIGNATURE, PRINTED NAME, AND LICENSE NUMBER(IF
 APPLICABLE) OF THE PERSON RESPONSIBLE FOR THE DESIGN.
 THIS INCLUDES THE LOAD CALCULATION SHEET AND RISER
 DIAGRAM. PROVIDE CORRECTION. WPB FBC 107.1, 107.2.1
 3. RISER DIAGRAM SHOWS THE NEW 200 AMP TRANSFER SWITCH
 FEEDING THE LOAD CONTROL MODULE. IT SEEMS THAT THIS
 TRANSFER SWITCH SHOULD FEED A PANEL, WHICH THEN FEEDS
 THE LOAD CONTROL MODULE TO THE LOADS THAT ARE BEING
 MANAGED. ALSO, HOW IS THE WHOLE HOUSE ON THE GENERATOR
 WHEN THERE IS STILL A 100 AMP MAIN THAT IS NOT
 CONNECTED TO THE GENERATOR? PROVIDE CLARIFICATION
 AND/OR CORRECTION. SHOW ALL LOADS BEING MANAGED. NEC
 215.5; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  