2018-06-15 07:04:21 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND |
| SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE |
| ELECTRICAL CONTRACTOR QUALIFIER. IF THERE IS NOT ANY |
| ELECTRICAL WORK INCLUDED WITH THIS PERMIT, STATE THAT |
| ON PLAN. FS 471.003(2)(H); 471.025; WPB FBC 107.2.1, |
| 107.3.5 |
| |
| INCLUDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC |
| 107.3.5; FBC RE E3706.2, E3902 |
| |
| 2.. PROVIDE UL/NRTL LISTING FOR ELEVATOR ASSEMBLY AND |
| ASSOCIATED EQUIPMENT 110.3B NEC; FBC 107 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |