2018-09-02 09:19:29 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| 1. PROVIDE AIC RATING OF PANELS. NEC 110.3, 110.9 (NOT |
| ADDRESSED.) |
| 2. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT |
| CURRENT AT NEW PANELS TO CONFIRM AIC RATING IS |
| ADEQUATE. NEC 110.10 (NOT ADDRESSED.) |
| 3. PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE |
| MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT |
| AVAILABLE PER NEC 110.24. (NOT ADDRESSED.) |
| 4. PROVIDE NOTE THAT GFCI PROTECTION FOR DRINKING |
| FOUNTAIN MUST BE READILY ACCESSIBLE. NEC 422.5, 422.52 |
| (NOT ADDRESSED.) |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |
| NOTE: PROPOSED USE IS INSTITUTIONAL "I-4" NOT |
| EDUCATIONAL "E". SEE NUMBER OF CHILDREN AND AGES. |