| 09/28/18 TALKED TO RICHARD ELLIOT (OWNER). TOLD HIM TO |
| READ COMMENTS AND BUILDING REVIEW COULD BE APPROVED |
| WITH PROVISO (FEES MAY APPLY). |
| |
| |
| TENANT BUILD OUT AND CHANGE OF OCCUPANCY SECOND |
| BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |
| 1-IMPACT FEES |
| BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES |
| MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE |
| SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM |
| BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH |
| THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT |
| MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE |
| THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL |
| PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
| |
| 2- SHEET A0.01-COVER SHEET: |
| A) OK |
| |
| B) A NEW CERTIFICATE OF OCCUPANCY WILL BE REQUIRED. |
| SEC. 1001.3 FBC EXISTING BUILDING. (PROVISO) |
| |
| C)OK |
| |
| D) OK |
| |
| E) OK |
| |
| 3- SHEET A1.01-PLAYGROUND/SITE PLAN: |
| A)SPECIFY SIZE OF ALL EXIT GATES FROM FENCED PLAYGROUND |
| AREAS AS REQUIRED BY SEC. 1006.2.2.4 FBC. |
| |
| B) OK. |
| |
| PROVISO: PROVIDE COMPLETE INFORMATION FOR PLAY AREAS |
| EQUIPMENT UNDER A SEPARATE PERMIT SHOWING COMPLIANCE |
| WITH SEC. 240 FBC- ACCESSIBILITY FOR THE ITEMS THAT |
| APPLY IN THIS PROJECT. |
| C) PLAY AREAS: SHOW COMPLIANCE WITH SEC. 240 AND 1008 |
| FBC- ACCESSIBILITY FOR THE ITEMS THAT APPLY IN THIS |
| PROJECT. |
| |
| |
| 4- SHEET A2.00- LIFE SAFETY PLAN: |
| A) OK. |
| |
| B) OK. |
| |
| C) OK |
| |
| (2)SHOW COMPLIANCE WITH CONSTRUCTION AND OPENINGS SEC. |
| 1028.4.2 FBC. THE WIDTH OF THE EGRESS COURT IS LESS |
| THAN 10FEET. |
| NOTE: NEED NOT LESS THAN 3/4 HOUR FIRE RATING. (NOT 20 |
| MIN.) |
| |
| (3)SHOW COMPLIANCE WITH THE ACCESS TO A PUBLIC WAY. |
| SEC. 1028.5 FBC. NOTE: THE EGRESS ACCESS NEED TO BE |
| ACCESSIBLE. SEC. |
| 207.1 FBC ACCESSIBLE. SHOW ON PLANS FLOOR/GROUND |
| SURFACES LEADING TO ALL GATES (NORTH, SOUTH AND EAST). |
| THIS INFORMATION MAY BE PROVIDED ON SITE PLAN SHEET |
| A1.01. |
| |
| (4) OK. |
| |
| D) OK. |
| |
| E) OK. |
| |
| F) OK. |
| |
| 5- SHEET A2.01 - FLOOR PLAN: |
| A) TENANT SEPARATION WALL "P2". REVISE DETAIL 2/A8.01. |
| THERE IS INFORMATION FOR UL # U419 AND FOR UL # U465 ON |
| THE SAME DETAIL. DON'T MISMATCH BOTH ASSEMBLIES. |
| ALSO ON SHEET A8.01 THERE ARE TWO DETAILS #1 AND THERE |
| IS NOT DETAIL #6. COORDINATE WITH DETAILS ON WALL |
| LEGEND ON SHEET A2.01. |
| |
| B) OK |
| |
| C)SPECIFY DIMENSION FOR OPENING IN THE HALF HEIGHT |
| PARTITION LOCATED BETWEEN THE INFANTS CLASSROOMS. |
| |
| D)OK. |
| |
| E)OK. |
| |
| F) OK. |
| |
| 6- SHEET A4.00-SCHEDULES/DETAILS: |
| A) OK. |
| |
| B)OK. |
| |
| 7- OK. |
| |
| 8- OK. |
| |
| 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL) |
| A) NEW EXTERIOR EXIT DOOR S SHOWN ON PLANS. |
| NOTE: NOA 14-1021.03 SUBMITTED NEED TO BE COORDINATED |
| WITH REQUIRED 3/4 HOUR FIRE RATED DOOR. SEE ITEM |
| #4(C)(2) ABOVE. PROVIDE FIRE RATING FOR THIS DOOR. |
| |
| B) PRECAST LINTELS A SPECIFIED ON PLANS FOR NEW ENTRY |
| DOOR OPENING. |
| NOTE: PROVIDE ACTUAL NOA OR FLORIDA PRODUCT APPROVAL |
| NOT THE MANUFACTURER'S LITERATURE. |
| |
| 10-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 11-PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| |
| 12-PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS. |
| |
| |
| ****PROVISO: IF MORE THAN 100 CHILDREN LESS THAN 2 1/2 |
| YRS THEN SPRINKLERS ARE REQUIRED |
| |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |