2018-07-31 14:50:20 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. AT LEAST 1 SINK IN EACH ROOM SHALL COMPLY WITH FBC |
| ACC 212.3, 606 |
| |
| 2. GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| GRIPPING SURFACE, PER FBC ACC 609.4 |
| |
| 3. ALL WATER FOUNTAINS SHALL COMPLY WITH FBC ACC 211 |
| |
| 4. SHOW THE AGES OF THE CHILDREN ON THE FLOOR PLAN PER |
| ROOM. WPB AMEND TO FBC 107.2.1 |
| |
| 5. PROVIDE SIZING CALCULATIONS FOR THE GREASE |
| INTERCEPTOR. WPB AMEND TO FBC 107.2.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |
| |
2018-07-11 08:05:32 | NOTE: PROPOSED USE IS INSTITUTIONAL "I-4" NOT |
| EDUCATIONAL "E". SEE NUMBER OF CHILDREN AND AGES |