2018-07-10 16:03:24 | TENANT BUILD OUT AND CHANGE OF OCCUPANCY-BUILDING |
| REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |
| 1-IMPACT FEES |
| BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES |
| MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE |
| SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM |
| BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH |
| THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT |
| MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE |
| THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL |
| PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
| |
| 2- SHEET A0.01-COVER SHEET: |
| A) REVISE PROPOSED OCCUPANCY CLASSIFICATION. GROUP "E" |
| DAY CARE FACILITIES IS FOR CHILDREN OLDER THAN 2-1/2 |
| YEARS OLD. SEC. 305.2 FBC. ACCORDING TO SEC. 308.6 FBC |
| THE OCCUPANCY CLASSIFICATION FOR THE PROPOSED OCCUPANCY |
| IS "I-4" DAY CARE FACILITIES NOT "E" (MORE THAN 100 |
| CHILDREN). REVISE THE PREVIOUS TENANT NOTES, BUILDING |
| AND CONSTRUCTION DATA AND INTERIOR FINISHES INFORMATION |
| AS REQUIRED. PLANS NEED TO BE REVIEWED AS INSTITUTIONAL |
| I-4. |
| |
| B) A NEW CERTIFICATE OF OCCUPANCY WILL BE REQUIRED. |
| SEC. 1001.3 FBC EXISTING BUILDING. |
| SEC. 1001.3 CERTIFICATE OF OCCUPANCY REQUIRED. |
| A CERTIFICATE OF OCCUPANCY SHALL BE ISSUED WHERE A |
| CHANGE OF OCCUPANCY OCCURS THAT RESULTS IN A DIFFERENT |
| OCCUPANCY CLASSIFICATION AS DETERMINED BY THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| C)\REVISE EXISTING BUILDING CONSTRUCTION TYPE. |
| ACCORDING TO NEW BUILDING CITY RECORDS PERMIT #13060228 |
| THIS BUILDING IS CONSTRUCTION TYPE VB NOT TYPE IIIB. |
| NOTE: EXISTING BUILDING IS NON-SPRINKLERED. REVISE AS |
| REQUIRED. SEC. 601.1 FBC. |
| |
| D) REVISE TOTAL OCCUPANT LOAD. THE TOTAL OCCUPANT LOAD |
| OF 35S.F. NET FOR DAY CARE IS FOR ALL OCCUPANTS |
| INCLUDING STAFF, NOT JUST THE CHILDREN. NEED TO DELETE |
| THE 30 STAFF. ON THE OTHER HAND NEED TO ADD THE NUMBER |
| OF PEOPLE FOR OTHER AREAS LIKE KITCHEN, RECEPTION AND |
| JANITOR/LAUNDRY. REVISE AS REQUIRED USING TABLE |
| 1004.1.2 FBC. |
| |
| E) REVISE INTERIOR FINISHES INFORMATION. THERE IS NOT |
| TABLE 803.9. THE CORRECT TABLE IS IS TABLE 803.11 FBC. |
| |
| 3- SHEET A1.01-PLAYGROUND/SITE PLAN: |
| A)SHOW COMPLIANCE WITH THE TWO EXITS FROM FENCED |
| PLAYGROUND AREAS AS REQUIRED BY SEC. 1006.2.2.4 FBC. |
| |
| B) PLAY AREAS: SHOW COMPLIANCE WITH ACCESSIBLE ROUTES |
| SEC. 206.2.17. FBC- ACCESSIBILITY |
| |
| C) PLAY AREAS: SHOW COMPLIANCE WITH SEC. 240 FBC- |
| ACCESSIBILITY FOR THE ITEMS THAT APPLY IN THIS PROJECT. |
| |
| D) PLAY AREAS: SHOW COMPLIANCE WITH SEC. 1008 FBC- |
| ACCESSIBILITY FOR THE ITEMS THAT APPLY IN THIS PROJECT. |
| |
| |
| 4- SHEET A2.00- LIFE SAFETY PLAN: |
| A) TOTAL OCCUPANT LOAD ON DOOR REQUIREMENTS NOTE C IS |
| INCORRECT. COORDINATE WITH ITEM #2D ABOVE AND REVISE AS |
| REQUIRED. SEC. 1004.1 FBC. |
| |
| B) THE CORRIDOR CONTINUITY IS INTERRUPTED BY AN |
| INTERVENING ROOM (DRAMATIC PLAY CLASSROOM). REVISE FBC. |
| AS REQUIRED. SEC. 1020.6 FBC. |
| |
| C) SHOW COMPLIANCE WITH THE EXIT DISCHARGE REQUIREMENTS |
| AT THE FENCED AREAS: |
| 1)SHOW COMPLIANCE WITH THE WIDTH SEC. 1028.4.1 FBC. |
| NOTE: I LOOKS LIKE THE WIDTH OF THE "EGRESS COURT" ON |
| BY THE TWO |
| CLASSROOMS ON THE NORTH EAST CORNER OF THE BUILDING |
| DOESN'T COMPLY WITH SEC. 1005.7.1 FBC. THE DOOR REDUCES |
| THE WIDTH BY MORE THAN ONE-HALF. REVISE AS REQUIRED TO |
| COMPLY. |
| |
| (2)SHOW COMPLIANCE WITH CONSTRUCTION AND OPENINGS SEC. |
| 1028.4.2 FBC. THE WIDTH OF THE EGRESS COURT IS LESS |
| THAN 10FEET. |
| |
| (3)SHOW COMPLIANCE WITH THE ACCESS TO A PUBLIC WAY. |
| SEC. 1028.5 FBC. NOTE: THE EGRESS ACCESS NEED TO BE |
| ACCESSIBLE. SEC. |
| 207.1 FBC ACCESSIBLE. SHOW ON PLANS FLOOR/GROUND |
| SURFACES LEADING TO ALL GATES (NORTH, SOUTH AND EAST). |
| THIS INFORMATION MAY BE PROVIDED ON SITE PLAN SHEET |
| A1.01. |
| |
| (4) SWING OF GATES ON PLAYGROUND AREA NEED TO BE IN THE |
| DIRECTION OF TRAVEL FOR AREAS WITH MORE THAN 50 PEOPLE. |
| THERE IS |
| A CONFLICT WITH THE GATE LOCATED BETWEEN THE OLDER KIDS |
| AND INFANTS/TODDLERS. REVISE AS REQUIRED. SEC. |
| 1010.1.2.1 FBC. |
| THIS INFORMATION MAY BE PROVIDED ON SITE PLAN SHEET |
| A1.01. |
| |
| D) THE NUMBER OF EXITS SHOWN ON THE EXIT REQUIREMENTS |
| TABLE IN THE MIDDLE OF THE SHEET IS NOT CLEAR. THERE |
| ARE 8 EXITS SHOWN ON PLAN NOT 11. NOTE: EXIT AND EXIT |
| ACCESS DOORWAY ARE NOT THE SAME THING. SEE DEFINITIONS |
| ON CHAPTER 2. ALSO, FOR CLARIFICATION THERE ARE ONLY 3 |
| EXITS LOCATED IN THE CORRIDOR. THE OTHER 5 EXITS ARE |
| THE REQUIRED 2ND EXITS FOR THE INDIVIDUAL ROOMS. SEC. |
| 1006.2.2.4 FBC. |
| |
| E) EXIT SIGN IS MISSING ON BOTH SIDES OF EXIT ACCESS |
| DOOR BETWEEN THE TWO INFANT CLASSROOMS. SEC. 1013.1 |
| FBC. REVISE ELECTRICAL PLANS AS REQUIRED. |
| |
| F) THERE ARE NOT EXIT SIGNS IN THE CORRIDOR INDICATING |
| THE DIRECTION OF EGRESS TRAVEL. SEC. 1013.1 FBC. REVISE |
| ELECTRICAL PLANS AS REQUIRED. NOTE:CHECK REQUIRED |
| DISTANCES ALSO. |
| |
| 5- SHEET A2.01 - FLOOR PLAN: |
| A) TWO HOUR TENANT SEPARATION WALL "P2". ASSEMBLY |
| UL-U465 SPECIFIED ON DETAIL 2/A8.01 DOESN'T CORRESPOND |
| TO 2 HOUR FIRE RATED WALL ASSEMBLY AND IT DOESN'T MATCH |
| THE UL-U465 ASSEMBLY EITHER. REVISE AS REQUIRED. |
| PROVIDE 2 HR FIRE RATED ASSEMBLY THAT PROVIDE FIRE |
| RESISTANCE FROM BOTH SIDES. TABLE 508.4 FBC |
| |
| B) TWO HOUR TENANT SEPARATION WALL "P2". HEAD/WALL |
| JOINT TERMINATION SYSTEM NO HW-D-0020 SPECIFIED ON |
| DETAIL 6/A8.01 DOESN'T MATCH WALL AND CEILING |
| ASSEMBLIES IN THIS PROJECT. REVISE AS REQUIRED. TABLE |
| 508.4 FBC. NOTE: ACCORDING TO CITY RECORDS FOR THE |
| CONSTRUCTION OF THE SHELL, THERE IS NOT CONCRETE IN THE |
| ROOF ASSEMBLY. |
| |
| C)CLARIFY/REVISE INFORMATION FOR DOOR IN THE HALF |
| HEIGHT PARTITION LOCATED BETWEEN THE INFANTS |
| CLASSROOMS. CLARIFY SIZE OF DOOR. COORDINATE WITH EXIT |
| SIGN REQUESTED ON ITEM #4E ABOVE. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| D)PROVIDE ALL DIMENSIONS FOR ALL BATHROOMS SHOWN ON THE |
| FLOOR PLAN. SEC. 604 FBC-ACCESSIBILITY. |
| |
| E)REVISE INFORMATION ON DETAIL 4/A4.00 FOR WINDOW W1 |
| SPECIFIED ON FLOR PLAN. THE DISTANCE OF GLAZING FROM |
| THE DOOR IS WITHIN 24" NOT 12". REVISE AS REQUIRED. |
| SEC. 2406.4 FBC. |
| |
| F) REVISE FINISH NOTES AT THE BOTTOM OF ROOM FINISH |
| SCHEDULE. INFORMATION DOESN'T MATCH INFORMATION SHOWN |
| ON SHEET A0.01. REVISE CLASS OF FINISHES TO MATCH AND |
| PROVIDE CORRECT TABLE NUMBER. COORDINATE WITH ITEM #2E |
| ABOVE. TABLE 803.11 FBC. |
| |
| 6- SHEET A4.00-SCHEDULES/DETAILS: |
| A) REVISE NOTE AT THE BOTTOM OF DOOR SCHEDULE "ALL |
| DOORS TO COMPLY W/ FBC 1008.1.9". THERE IS NOT SUCH |
| SECTION. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| B)REVISE INFORMATION ON DETAIL 4/A4.00 FOR WINDOW W1 |
| SPECIFIED ON FLOR PLAN. THE DISTANCE OF GLAZING FROM |
| THE DOOR IS WITHIN 24" NOT 12". REVISE AS REQUIRED. |
| SEC. 2406.4 FBC. |
| |
| 7- PROVIDE FIRE SPRINKLERS INFORMATION AS REQUIRED BY |
| SEC. 107.3.5.1 CITY AMENDMENTS. |
| |
| 8- THE PROPOSED SCOPE OF WORK INCLUDES THE SHELL AREA |
| THAT WAS NOT AIR CONDITIONED AND A CHANGE OF |
| OCCUPANCY/USE. PROVIDE COMPLETE ENERGY CALCULATIONS (2 |
| COPIES), NOT JUST THE PRESCRIPTIVE FORM. SEE MECHANICAL |
| COMMENTS. SEC. C503.2 AND SEC. C505 FBC-ENERGY |
| CONSERVATION. |
| NOTE: PLEASE MAKE SURE ENERGY CALCULATIONS ARE PROPERLY |
| SIGNED AND SEALED BY THE REQUIRED DESIGN PROFESSIONALS |
| AND ALL THE INFORMATION IS PROVIDED. |
| |
| 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL) |
| A) NEW EXTERIOR EXIT DOOR S SHOWN ON PLANS. |
| |
| B) PRECAST LINTELS A SPECIFIED ON PLANS FOR NEW ENTRY |
| DOOR OPENING. |
| |
| 10-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 11-PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| |
| 12-PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS. |
| |
| |