Plan Review Notes For Permit 18060665 |
Permit Number |
18060665 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-28 11:17:23 | 1) THE CALCULATIONS FOR THE PROPANE TANK ANCHORAGE FROM | | TIE DOWN ENGINEERING ARE REQUIRED TO BE SIGNED AND | | SEALED BY AN ENGINEER LICENSED IN THE STATE OF FLORIDA | | PER FL. STATUTE 471.025, 471.003, 471.005, & FL. ADMIN. | | CODE RULE 61G15-23.001. THE DOCUMENTS ARE ADVERTISING | | AS "ENGINEERING". | | 61G15-23.001 SIGNATURE, DATE AND SEAL SHALL BE AFFIXED. | | (1) A PROFESSIONAL ENGINEER SHALL SIGN, DATE AND SEAL: | | (A) ALL FINAL PLANS, PRINTS, SPECIFICATIONS, REPORTS, | | OR OTHER DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE | | AND BEING FILED FOR PUBLIC RECORD; | | 2) SHOW THE LOCATION OF ALL PRESSURE REGULATORS.A | | SHUTOFF VALVE IS REQUIRED UPSTREAM OF EACH | | REGULATOR.2017 FBC-GAS VOLUME SEC.409.4. | | 3) SUBMIT THE SIZING TABLE FOR THE LOW PRESSURE SYSTEM. | | 2017 FBC-FUEL GAS SEC.402.3. | | 4) INDICATE THE TYPE AND SIZE OF THE PIPE FROM THE LP | | TANK TO THE CONNECTION WITH THE PE PIPE. | | | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|