2018-06-29 06:45:06ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. WORK TO BE PERFORMED UNCLEAR. APPLICATION SAYS "COPY
 SIGN". THIS IS A REVISION TO AN ALREADY ISSUED PERMIT.
 CHANGES TO PLANS NEED TO BE MARKED BY REVISION BUBBLES.
 PLEASE PROVIDE WRITTEN SCOPE OF WORK. FBC 107.2.1
  
 2. NO ELECTRICAL DRAWINGS SUBMITTED. PROVIDE ELECTRICAL
 PLAN FOR REVIEW, SIGNED AND SEALED BY A LICENSED DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. IF
 THERE IS NOT ANY ELECTRICAL WORK INCLUDED WITH THIS
 PERMIT, STATE THAT ON PLAN. FS 471.003(2)(H); 471.025;
 WPB FBC 107.2.1, 107.3.5
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved