Plan Review Notes For Permit 18060616 |
Permit Number |
18060616 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-27 13:28:33 | 1ST REVIEW FBC-20170MECHANICAL | | PERMIT #18060616 | | 6/27/18 | | | | CODES IN EFFECT: | | FBC M- FLORIDA MECHANICAL CODE- 2010 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2010 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M2.90-GS12: MISSING FIRE DAMPERS FOR DUCT | | TRUNK PENETRATIONS AT THE SOUTH AND EAST FIRE-RATED | | WALLS OF THE SUITE- SECTION 607.5.2 & 697.5.3 FBC-10 | | MECHANICAL. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|