2018-06-14 17:22:181ST REVIEW FBC-2014 MECHANICAL
 REVISION #18060593
 MASTER #17101112
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE FIFTH EDITION 2014
 FBC M- FLORIDA MECHANICAL CODE FIFTH EDITION 2014
 FBC EC- FLORIDA ENERGY CONSERVATION CODE FIFTH EDITION
 2014
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC FIFTH
 EDITION 2014
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN
 FOR THE ERV AND SUBMIT MANUFACTURER'S SPECIFICATIONS-
 SECTION 514.1 FBC M.
  
 2) M-1: THE AIR BALANCE CALCULATION DOES NOT INCLUDE
 THE REQUIRED 488.4 CFMS OF EXHAUST FROM THE THE BEAUTY
 SALON. THE REQUIREMENT FOR THE ERV IS BASED ON THAT
 AMOUNT OF EXHAUST AIR WHICH IS 94% OF THE 517.68 CFMS
 OUTSIDE AIR BEING SUPPLIED FOR THE OCCUPANTS- SEE TABLE
 C403.2.6 FBC EC. THE TYPICAL INSTALLATION UNDER THESE
 CIRCUMSTANCES IS TO DUCT THE EXHAUST AIR INTO THE ERV
 SO THAT THE AIR CAN BE EXHAUSTED, BUT THE ENERGY CAN BE
 CAPTURED ON THE HEAT WHEEL TO MIX WITH THE INCOMING
 OUTSIDE AIR. THE CURRENT PLAN SHOWING THE EXHAUST FROM
 THE SALON DIRECTLY DISCHARGED TO THE OUTDOORS IS NOT IN
 COMPLIANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  