2018-06-14 17:22:18 | 1ST REVIEW FBC-2014 MECHANICAL |
| REVISION #18060593 |
| MASTER #17101112 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE FIFTH EDITION 2014 |
| FBC M- FLORIDA MECHANICAL CODE FIFTH EDITION 2014 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE FIFTH EDITION |
| 2014 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC FIFTH |
| EDITION 2014 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M-1: PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN |
| FOR THE ERV AND SUBMIT MANUFACTURER'S SPECIFICATIONS- |
| SECTION 514.1 FBC M. |
| |
| 2) M-1: THE AIR BALANCE CALCULATION DOES NOT INCLUDE |
| THE REQUIRED 488.4 CFMS OF EXHAUST FROM THE THE BEAUTY |
| SALON. THE REQUIREMENT FOR THE ERV IS BASED ON THAT |
| AMOUNT OF EXHAUST AIR WHICH IS 94% OF THE 517.68 CFMS |
| OUTSIDE AIR BEING SUPPLIED FOR THE OCCUPANTS- SEE TABLE |
| C403.2.6 FBC EC. THE TYPICAL INSTALLATION UNDER THESE |
| CIRCUMSTANCES IS TO DUCT THE EXHAUST AIR INTO THE ERV |
| SO THAT THE AIR CAN BE EXHAUSTED, BUT THE ENERGY CAN BE |
| CAPTURED ON THE HEAT WHEEL TO MIX WITH THE INCOMING |
| OUTSIDE AIR. THE CURRENT PLAN SHOWING THE EXHAUST FROM |
| THE SALON DIRECTLY DISCHARGED TO THE OUTDOORS IS NOT IN |
| COMPLIANCE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |
| IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. |
| |