2018-06-13 11:25:26PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ROOF COVERING ASSEMBLY THAT IS SELECTED ON PAGE
 33 OF NOA NO. 17-1004.09 IS DIFFERENT FROM THE ONE THAT
 IS LISTED ON THE CONTRACT THAT WAS SUBMITTED. PLEASE
 CLARIFY. FBC 107.2.1
  
 2) THE ASSEMBLY THAT MATCHES THE CONTRACT ON PAGE 10
 AND 11 OF THE NOA, HAS A DESIGN PRESSURE OF -52.5 PSF.
 WHICH IS NOT ADEQUATE FOR A FLAT ROOF ON A STRUCTURE
 WITH A 15' MEAN ROOF HEIGHT IN EXPOSURE C WITH A 170
 MPH VULT WIND SPEED. IF THIS ASSEMBLY IS TO BE USED,
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING WILL BE REQUIRED. SEE LIMITATION #7 ON PAGE
 34 OF THE NOA. FBC-R905.11.3