2018-06-13 11:25:26 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE ROOF COVERING ASSEMBLY THAT IS SELECTED ON PAGE | | 33 OF NOA NO. 17-1004.09 IS DIFFERENT FROM THE ONE THAT | | IS LISTED ON THE CONTRACT THAT WAS SUBMITTED. PLEASE | | CLARIFY. FBC 107.2.1 | | | | 2) THE ASSEMBLY THAT MATCHES THE CONTRACT ON PAGE 10 | | AND 11 OF THE NOA, HAS A DESIGN PRESSURE OF -52.5 PSF. | | WHICH IS NOT ADEQUATE FOR A FLAT ROOF ON A STRUCTURE | | WITH A 15' MEAN ROOF HEIGHT IN EXPOSURE C WITH A 170 | | MPH VULT WIND SPEED. IF THIS ASSEMBLY IS TO BE USED, | | SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED | | FASTENING WILL BE REQUIRED. SEE LIMITATION #7 ON PAGE | | 34 OF THE NOA. FBC-R905.11.3 |
|