2018-07-05 16:43:571ST REVIEW: FBC 2017 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDE FOR SUMP PUMP. PER WPB AMEND TO FBC 107.2.1
 ADDITIONAL INFORMATION REQUIRED.
  
 2. PER MANUFACTURE AIR ADMITTANCE VALVES ARE NOT
 ALLOWED FOR INSTALLATION ON LIBERTY PUMP #405.
  
 3. A BACKFLOW IS REQUIRED ON THE REFRIGERATOR ICE
 MACHINE. PER FBC PL 608.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  