2018-08-28 04:14:03 | 1) THE EXISTING GAS PLAN ON FILE IN THE CITY OF WPB |
| RECORDS SHOWS A FUTURE LINE FOR A POOL HEATER WITH A |
| BTU LOAD OF 400,000. THIS IS NOT SHOWN ON THE SUBMITTED |
| GAS DRAWING. THIS " FUTURE" OUTLET AND BTU LOAD MUST BE |
| INCLUDED IN THE TOTAL BTU LOAD OF THE SYSTEM. 2017 FBCR |
| SEC. G2412.3, G2412.4, G2412.8. |
| 2) THE SUBMITTED GAS DRAWING SHOWS THE EXISTING SYSTEM |
| TO THE INTERIOR AS BEING A LESS THAN 2 PSI SYSTEM YET |
| THE GAS PLAN ON FILE IN THE CITY RECORDS SHOWS THE |
| INTERIOR PIPING TO BE A 2 PSI SYSTEM. CLARIFY. NOTE - |
| AT A LESS THAN 2 PSI SYSTEM THE INTERIOR PIPING OF CSST |
| IS ALL UNDERSIZED FOR A DISTANCE OF 110 FEET AS SHOWN |
| ON THE PLAN THE SUBMITTED SIZING TABLE. |
| 3) THE MINIMUM SIZE SLEEVE FOR THE 3/4 INCH PE PIPE |
| SHALL BE 1 1/4 INCHES IN DIAMETER. |
| 4) THE GAS PLAN ON FILE IN CITY RECORDS SHOWS THE |
| EXISTING WATER HEATER AS 100,000 BTU'S BUT THE NEW |
| SUBMITTED GAS PLAN SHOWS THE EXISTING WATER HEATER AS |
| 50,000 BTU'S. CLARIFY. |
| 5) THE EXISTING GAS PLAN ON FILE IN CITY RECORDS SHOWS |
| AN EXISTING GAS GRILL WITH A BTU LOAD OF 60,000. THIS |
| IS NOT SHOWN ON THE EXISTING SYSTEM ON THE SUBMITTED |
| GAS DRAWING. CLARIFY. |
| 6) THE EXISTING GAS PLAN ON FILE IN CITY RECORDS SHOWS |
| TWO FIREPLACES AT 50,000 BTU'S EACH AND THE SUBMITTED |
| GAS PLAN SHOWS ONE EXISTING FIREPLACE AT 90,000 BTU'S . |
| CLARIFY. |
| NOTE: ACCORDING TO THE GAS PLAN ON FILE IN CITY RECORDS |
| THE EXISTING BTU LOAD IS 750,000 AND THE SUBMITTED GAS |
| PLAN SHOWS THE EXISTING BTU LOAD AS 240,000. CLARIFY. |
| 7) THE MINIMUM SIZE SCHEDULE 40 METALLIC PIPE AT THE |
| OUTLET OF THE GAS METER SHALL BE 1 INCH. 2017 FBCR |
| TABLE G2413.4 (2) . |
| 8) SHOW THE LOCATION OF THE GAS PIPING TO THE GENERATOR |
| ON BOTH COPIES OF THE SURVEY. WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 9) IF THE EXISTING INTERIOR GAS PIPING WILL REMAIN AS A |
| 2 PSI SYSTEM, PLACE A NOTE ON THE PLAN THAT EXISTING |
| REGULATORS ARE LOCATED AT EACH APPLIANCE. |
| |
| ****NOTE*** - I HAVE PLACED A COPY OF THE ORIGINAL GAS |
| PLAN AND SUBSEQUENT REVISIONS IN THE APPLICATION TO BE |
| USED AS REFERENCE. |