Plan Review Notes
Plan Review Notes For Permit 18060545
Permit Number 18060545
Review Stop G
Sequence Number 2
Notes
Date Text
2018-08-28 04:14:031) THE EXISTING GAS PLAN ON FILE IN THE CITY OF WPB
 RECORDS SHOWS A FUTURE LINE FOR A POOL HEATER WITH A
 BTU LOAD OF 400,000. THIS IS NOT SHOWN ON THE SUBMITTED
 GAS DRAWING. THIS " FUTURE" OUTLET AND BTU LOAD MUST BE
 INCLUDED IN THE TOTAL BTU LOAD OF THE SYSTEM. 2017 FBCR
 SEC. G2412.3, G2412.4, G2412.8.
 2) THE SUBMITTED GAS DRAWING SHOWS THE EXISTING SYSTEM
 TO THE INTERIOR AS BEING A LESS THAN 2 PSI SYSTEM YET
 THE GAS PLAN ON FILE IN THE CITY RECORDS SHOWS THE
 INTERIOR PIPING TO BE A 2 PSI SYSTEM. CLARIFY. NOTE -
 AT A LESS THAN 2 PSI SYSTEM THE INTERIOR PIPING OF CSST
 IS ALL UNDERSIZED FOR A DISTANCE OF 110 FEET AS SHOWN
 ON THE PLAN THE SUBMITTED SIZING TABLE.
 3) THE MINIMUM SIZE SLEEVE FOR THE 3/4 INCH PE PIPE
 SHALL BE 1 1/4 INCHES IN DIAMETER.
 4) THE GAS PLAN ON FILE IN CITY RECORDS SHOWS THE
 EXISTING WATER HEATER AS 100,000 BTU'S BUT THE NEW
 SUBMITTED GAS PLAN SHOWS THE EXISTING WATER HEATER AS
 50,000 BTU'S. CLARIFY.
 5) THE EXISTING GAS PLAN ON FILE IN CITY RECORDS SHOWS
 AN EXISTING GAS GRILL WITH A BTU LOAD OF 60,000. THIS
 IS NOT SHOWN ON THE EXISTING SYSTEM ON THE SUBMITTED
 GAS DRAWING. CLARIFY.
 6) THE EXISTING GAS PLAN ON FILE IN CITY RECORDS SHOWS
 TWO FIREPLACES AT 50,000 BTU'S EACH AND THE SUBMITTED
 GAS PLAN SHOWS ONE EXISTING FIREPLACE AT 90,000 BTU'S .
 CLARIFY.
 NOTE: ACCORDING TO THE GAS PLAN ON FILE IN CITY RECORDS
 THE EXISTING BTU LOAD IS 750,000 AND THE SUBMITTED GAS
 PLAN SHOWS THE EXISTING BTU LOAD AS 240,000. CLARIFY.
 7) THE MINIMUM SIZE SCHEDULE 40 METALLIC PIPE AT THE
 OUTLET OF THE GAS METER SHALL BE 1 INCH. 2017 FBCR
 TABLE G2413.4 (2) .
 8) SHOW THE LOCATION OF THE GAS PIPING TO THE GENERATOR
 ON BOTH COPIES OF THE SURVEY. WPB AMEND. TO FBC SEC.
 107.2.1.
 9) IF THE EXISTING INTERIOR GAS PIPING WILL REMAIN AS A
 2 PSI SYSTEM, PLACE A NOTE ON THE PLAN THAT EXISTING
 REGULATORS ARE LOCATED AT EACH APPLIANCE.
  
 ****NOTE*** - I HAVE PLACED A COPY OF THE ORIGINAL GAS
 PLAN AND SUBSEQUENT REVISIONS IN THE APPLICATION TO BE
 USED AS REFERENCE.
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  