Plan Review Notes
Plan Review Notes For Permit 18060517
Permit Number 18060517
Review Stop P
Sequence Number 4
Notes
Date Text
2019-02-05 12:05:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 4TH REVIEW; DENIED
  
 COMMENTS NOTED BELOW ARE A RESTATEMENT OF PREVIOUS
 COMMENTS WHICH HAVE NOT BEEN ADDRESSED.
 1. RE: PLAN SHEET P0.1; PLUMBING FIXTURE SCHEDULE,
 HLAV. SPECIFY IN THE FIXTURE DESCRIPTION AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3. TO COMPLY WITH FBC PL 416.5 PER WPB
 FPC 107.2.1.
 2. PROVIDE A DETAIL OF THE WATER HEATER AND HOT WATER
 RECIRC PUMP SHOWING THE FOLLOWING IN ACCORDANCE WITH
 WPB FBC 107.2.1:
 A) COLD AND COLD WATER PIPING ARRANGEMENT INCLUDING ALL
 VALVES IN ACCORDANCE WITH THE REQUIREMENTS OF FBC PL
 CHAPTER 6
 B) THERMAL EXPANSION DEVICE REQUIRED ON COLD WATER
 SUPPLY TO WATER HEATER IN ACCORDANCE WITH FBC PL 607.3
 C) T&P RELIEF VALVE AND DISCHARGE INCLUDING TERMINATION
 IN ACCORDANCE WITH FBC PL 504.1, 504.4, 504.4.1, 504.5
 AND 504.6 504.7, 504.7.1 AND 504.7.2.
 D) WATER HEATER PAN AND DRAIN INCLUDING TERMINATION IN
 ACCORDANCE WITH FBC PL 504.7, 504.7.1 AND 504.7.2.
  
 PLEASE NOTE THAT SUBMITTED PLAN PAGE P0.1 IS REV 1
 DATED 8/30/18 AND IT WAS NOTED ON THE LAST REVIEW THAT
 THERE WERE TWO (2) PLAN PAGES P0.1 ONE OF WHICH WAS REV
 1 AND THE OTHER WHICH WAS REV 2. IT IS POSSIBLE THAT
 THE WRONG P0.1 WAS SUBMITTED AND THAT THE P0.1 REV 2
 HAS THE REQUIRED INFORMATION.
 SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS. WHEN RESUBMITTING,
 IT IS HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING
 EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715