2019-02-05 12:05:52 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 4TH REVIEW; DENIED |
| |
| COMMENTS NOTED BELOW ARE A RESTATEMENT OF PREVIOUS |
| COMMENTS WHICH HAVE NOT BEEN ADDRESSED. |
| 1. RE: PLAN SHEET P0.1; PLUMBING FIXTURE SCHEDULE, |
| HLAV. SPECIFY IN THE FIXTURE DESCRIPTION AN APPROVED |
| WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| 1070 OR CSA B125.3. TO COMPLY WITH FBC PL 416.5 PER WPB |
| FPC 107.2.1. |
| 2. PROVIDE A DETAIL OF THE WATER HEATER AND HOT WATER |
| RECIRC PUMP SHOWING THE FOLLOWING IN ACCORDANCE WITH |
| WPB FBC 107.2.1: |
| A) COLD AND COLD WATER PIPING ARRANGEMENT INCLUDING ALL |
| VALVES IN ACCORDANCE WITH THE REQUIREMENTS OF FBC PL |
| CHAPTER 6 |
| B) THERMAL EXPANSION DEVICE REQUIRED ON COLD WATER |
| SUPPLY TO WATER HEATER IN ACCORDANCE WITH FBC PL 607.3 |
| C) T&P RELIEF VALVE AND DISCHARGE INCLUDING TERMINATION |
| IN ACCORDANCE WITH FBC PL 504.1, 504.4, 504.4.1, 504.5 |
| AND 504.6 504.7, 504.7.1 AND 504.7.2. |
| D) WATER HEATER PAN AND DRAIN INCLUDING TERMINATION IN |
| ACCORDANCE WITH FBC PL 504.7, 504.7.1 AND 504.7.2. |
| |
| PLEASE NOTE THAT SUBMITTED PLAN PAGE P0.1 IS REV 1 |
| DATED 8/30/18 AND IT WAS NOTED ON THE LAST REVIEW THAT |
| THERE WERE TWO (2) PLAN PAGES P0.1 ONE OF WHICH WAS REV |
| 1 AND THE OTHER WHICH WAS REV 2. IT IS POSSIBLE THAT |
| THE WRONG P0.1 WAS SUBMITTED AND THAT THE P0.1 REV 2 |
| HAS THE REQUIRED INFORMATION. |
| SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS MAY |
| RESULT IN NEW PLAN REVIEW COMMENTS. WHEN RESUBMITTING, |
| IT IS HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING |
| EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| REMAIN IN PACKAGE AND BE MARKED "VOID". |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |