2019-01-08 11:57:07 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 18060517 |
| ADD: 770 NORTHPOINT PKWY SUITE: 100 |
| CONT: LEIGHTON MCGINN |
| TEL: 561-308-2729 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 3RD REVIEW |
| DATE: TUES. JAN. 08/2019 |
| ACTION: DENIED |
| |
| 1-3) COMPLIED. |
| |
| NOTICE. 4X FEE / NOTICE!!!!! FLORIDA STATUTE |
| 553.80(2)(B). WITH RESPECT TO EVALUATION OF DESIGN |
| PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS |
| IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE |
| FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT |
| DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE |
| TIMES FOR FAILURE TO CORRECT A CODE VIOLATION |
| SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, |
| INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, |
| STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, |
| VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS |
| SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF |
| THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO |
| CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH |
| TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED |
| FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT |
| OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS |
| REVIEW. |
| |
| 4) 3RD REQUEST. THE PLANS SHEET A2 SHOWS THERE IS A LAB |
| IN THIS TENANT SPACE. RESPONSE INDICATES WILL SUBMIT |
| LATER UNDER A SEPARATE PERMIT. TO DO THIS YOU WILL NEED |
| TO REMOVE THE LAB FROM THE SCOPE OF WORK. PLEASE BE |
| AWARE UNDER THE BUILDING REVIEW AND MECHANICAL REVIEW |
| THE REQUIREMENTS FOR A LAB WILL REQUIRE RATED WALLS |
| VENTILATION REQUIREMENTS OTHER THAN A OFFICE (BUSINESS |
| OCCUPANCY) AND THE REQUIREMENTS UNDER 307 HAZARDOUS |
| MATERIAL, TABLE 307.1(1) MAXIMUM ALLOWABLE QUANTITIES |
| OF MATERIALS PER CONTROL AREAS. CONTROL AREAS SEE 2017 |
| FBC-B SECTION 414.2 CONTROL AREAS. CONTROL AREAS SHALL |
| COMPLY WITH SECTIONS 414.2.1 THROUGH414.2.5 AND THE |
| FLORIDA FIRE PREVENTION CODE. |
| |
| 5-6) COMPLIED. |
| |