Plan Review Notes
Plan Review Notes For Permit 18060517
Permit Number 18060517
Review Stop P
Sequence Number 2
Notes
Date Text
2018-10-09 13:07:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. THE ACCESSIBILITY CODE REQUIRES A MINIMUM OF 1 SINK
 IN EACH TYPE OF ACCESSIBLE ROOM COMPLY WITH FBC ACC 606
 PER FBC ACC 212.3. THIS IS A SECOND REQUEST. PLEASE
 NOTE THAT THE ARCHITECT HAS NOT PROVIDED THIS
 INFORMATION ON THE PLANS AND NEEDS TO DO SO BEFORE THE
 PLUMBING PERMIT APPLICATION CAN BE APPROVED. THE
 PROVIDED INFORMATION BY THE ARCHITECT NEEDS TO INCLUDE
 SUCH THINGS AS THE DESIGNATED ACCESSIBLE ROOM (IE. EXAM
 RM #4), MILL WORK PLAN AND ELEVATION VIEWS, AND
 POSSIBLY ANOTHER DESIGNATED PLUMBING FIXTURE IN THE
 PLUMBING FIXTURE SCHEDULE.
 2. RE: PLAN SHEET P0.1; PLUMBING FIXTURE SCHEDULE,
 HLAV. SPECIFY IN THE FIXTURE DESCRIPTION AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3. TO COMPLY WITH FBC PL 416.5 PER WPB
 FPC 107.2.1. THIS IS A SECOND REQUEST.
 3. PROVIDE A DETAIL OF THE WATER HEATER AND HOT WATER
 RECIRC PUMP SHOWING THE FOLLOWING IN ACCORDANCE WITH
 WPB FBC 107.2.1:
 A. HOT AND COLD WATER PIPING ARRANGEMENT INCLUDING ALL
 VALVES IN ACCORDANCE WITH THE REQUIREMENTS OF FBC PL
 CHAPTER 6.
 B. THERMAL EXPANSION DEVICE REQUIRED ON COLD WATER
 SUPPLY TO WATER HEATER IN ACCORDANCE WITH FBC PL 607.3
 C. T&P RELIEF VALVE AND DISCHARGE INCLUDING TERMINATION
 IN ACCORDANCE WITH FBC PL 504.1, 504.4, 504.4.1, 504.5
 AND 504.6 504.7, 504.7.1 AND 504.7.2.
 D. WATER HEATER PAN AND DRAIN INCLUDING TERMINATION IN
 ACCORDANCE WITH FBC PL 504.7, 504.7.1 AND 504.7.2.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715