2018-10-10 11:42:062ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18060517
 10/10/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN RESPONSE TO COMMENT #2 FRO THE 1ST REVIEW WHICH
 IS PRINTED BELOW, THE EOR IS STATING IN RESPONSE THAT A
 LETTER FROM THE OWNERSHIP IS TO BE PROVIDED TO ADDRESS
 THE USE OF THE LAB ROOM. THE LETTER WAS NOT SUBMITTED.
 PLEASE NOTE RHAT A LAB ROOM SHALL BE PROVIDED WITH AN
 EXHAUST VENTILATION SYSTEM, AND AIR RECIRCULATED FROM
 THE ROOM SHALL BE LIMITED TO 10%- SEE TABLE 403.3.1.1
 AND FOOTNOTE G
  
 2) THE PLANS SHOW A LAB ROOM. REFER TO SECTION 510.1
 FBC M AND CLARIFY WHAT PROCESSES ARE TO TAKE PLACE IN
 THE ROOM, AND WHAT CHEMICALS, IF ANY, ARE STORED IN THE
 ROOM AND THEIR QUANTITIES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER