Plan Review Notes
Plan Review Notes For Permit 18060517
Permit Number 18060517
Review Stop B
Sequence Number 1
Notes
Date Text
2018-07-02 07:48:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 2. SEPARATE PERMITS ARE REQUIRED FOR EACH SUITE, FBC
 107. PROVIDE VALUE FOR EACH UNIT.
  
 3. VALUE APPEARS LOW; PROVIDE CONTRACT AND COST
 BREAKDOWN FBC 109.
  
 4. FBC B 307, REVISE PLAN TO INDICATE PRODUCTS USED IN
 LAB, AMOUNTS.
  
 5. FBC EB 301.1, REVISE PLAN TO INDICATE METHOD
 SELECTED.
  
 6. NO FIRE RATED WALLS ARE SHOWN. INFORMATION ABOUT THE
 BUILDING, TYPICALLY CALLED A "CODE SUMMARY", WAS NOT
 PROVIDED - SPRINKLERED OR NOT, FIRE ALARM, BUILDING
 TYPE, AREA, ETC. NOT PROVIDED. FBC EB 803.6, THIS
 BUILDING WAS CONSTRUCTED WHEN TENANT SEPARATION AND
 OCCUPANCY SEPARATIONS WERE REQUIRED. COMPLIANCE WITH
 FLORIDA BUILDING CODE 2017, BUILDING NOT CLEAR; EITHER
 PROVIDE TENANT SEPARATION OR REVISE PLAN TO SHOW THAT
 THIS IS NOT REQUIRED.
  
  
  