2018-07-02 07:48:09 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED |
| SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| 2. SEPARATE PERMITS ARE REQUIRED FOR EACH SUITE, FBC |
| 107. PROVIDE VALUE FOR EACH UNIT. |
| |
| 3. VALUE APPEARS LOW; PROVIDE CONTRACT AND COST |
| BREAKDOWN FBC 109. |
| |
| 4. FBC B 307, REVISE PLAN TO INDICATE PRODUCTS USED IN |
| LAB, AMOUNTS. |
| |
| 5. FBC EB 301.1, REVISE PLAN TO INDICATE METHOD |
| SELECTED. |
| |
| 6. NO FIRE RATED WALLS ARE SHOWN. INFORMATION ABOUT THE |
| BUILDING, TYPICALLY CALLED A "CODE SUMMARY", WAS NOT |
| PROVIDED - SPRINKLERED OR NOT, FIRE ALARM, BUILDING |
| TYPE, AREA, ETC. NOT PROVIDED. FBC EB 803.6, THIS |
| BUILDING WAS CONSTRUCTED WHEN TENANT SEPARATION AND |
| OCCUPANCY SEPARATIONS WERE REQUIRED. COMPLIANCE WITH |
| FLORIDA BUILDING CODE 2017, BUILDING NOT CLEAR; EITHER |
| PROVIDE TENANT SEPARATION OR REVISE PLAN TO SHOW THAT |
| THIS IS NOT REQUIRED. |
| |
| |
| |