2018-06-27 13:12:331) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC
 7 ? 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION
 ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT
 REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED
 THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET
 FITTING ASSEMBLY (DRAIN COVER).
 2) SUBMIT A POOL PUMP CURVE THAT IS ENLARGED, CLEAR IN
 DETAIL AND LEGIBLE. WPB AMEND. TO FBC SEC. 107.2.1.
 3) IDENTIFY IN THE POOL PUMP SPECS WHICH MODEL POOL
 PUMP IS BEING INSTALLED.WPB AMEND. TO FBC SEC. 107.2.1.
 4) SUBMIT CLEAR AND LEGIBLE SPECIFICATIONS FOR THE
 CARTRIDGE FILTER. WPB AMEND. TO FBC SEC. 107.2.1.
 5) INDICATE ON THE PLANS IF THE POOL IS EQUIPPED WITH
 AN AUTO-FILL.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE HEAT
 PUMP. THE HEAT PUMP SHALL CCOMPLY WITH 2017 FBC -
 ENERGY SECS. R403.10.1, R403.10.2.
 7) THE HEAT PUMP SHALL HAVE A COP OF 4.0 WHEN TESTED IN
 ACCORDANCE WITH AHRI 1160. A TEST REPOR SHALL BE
 SUBMITTED TO VERIFY PROCEDURE COMPLIANCE. 2017
 FBC-ENERGY SEC.R403.10.5.
  