Plan Review Notes For Permit 18060482 |
Permit Number |
18060482 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-27 13:12:33 | 1) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE | | MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM | | ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN | | DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC | | 7 ? 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION | | ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT | | REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED | | THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET | | FITTING ASSEMBLY (DRAIN COVER). | | 2) SUBMIT A POOL PUMP CURVE THAT IS ENLARGED, CLEAR IN | | DETAIL AND LEGIBLE. WPB AMEND. TO FBC SEC. 107.2.1. | | 3) IDENTIFY IN THE POOL PUMP SPECS WHICH MODEL POOL | | PUMP IS BEING INSTALLED.WPB AMEND. TO FBC SEC. 107.2.1. | | 4) SUBMIT CLEAR AND LEGIBLE SPECIFICATIONS FOR THE | | CARTRIDGE FILTER. WPB AMEND. TO FBC SEC. 107.2.1. | | 5) INDICATE ON THE PLANS IF THE POOL IS EQUIPPED WITH | | AN AUTO-FILL. | | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE HEAT | | PUMP. THE HEAT PUMP SHALL CCOMPLY WITH 2017 FBC - | | ENERGY SECS. R403.10.1, R403.10.2. | | 7) THE HEAT PUMP SHALL HAVE A COP OF 4.0 WHEN TESTED IN | | ACCORDANCE WITH AHRI 1160. A TEST REPOR SHALL BE | | SUBMITTED TO VERIFY PROCEDURE COMPLIANCE. 2017 | | FBC-ENERGY SEC.R403.10.5. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|