2018-08-02 12:04:12 | 1ST REVIEW FBC-2017 MECHANICAL |
| REVISION #18060457 |
| MASTER #18020254 |
| 8/2/18 |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE SUBMITTED STRUCTURAL ENGINEERING FOR TIE DOWN OF |
| THE VRF CONDENSERS IS NOT ELECTRONICALLY SIGNED AND |
| SEALED BY THE ENGINEER WHO PREPARED THE DRAWING- |
| SECTION 61G15-23.005 FAC. A) THE DRAWING DOES NOT |
| SPECIFICALLY REFERENCE WHICH ROOFTOP UNITS ARE TO BE |
| INSTALLED IN ACCORDANCE WITH THE ENGINEERING. B) THE |
| DRAWING DOES NOT INDICATE LATERAL AND UPLIFT PRESSURES |
| BASED ON THE DESIGN CRITERIA AND THE DIMENSIONS OF THE |
| UNITS. C) THE DESIGN INDICATES THE UNITS NEED TO BE |
| STRAPPED TO THE SUPPORT BEAMS WHICH DOES NOT APPEAR TO |
| BE COMPATIBLE WITH THE DESIGN OF THE VRF CONDENSERS, |
| AND WILL ALSO REQUIRE REMOVAL OF STRAPPING FOR |
| SERVICING. PLEASE NOTE THAT COMPLETE WIND LOAD |
| ENGINEERING FOR ALL THE ROOFTOP UNITS IS REQUIRED |
| INCLUDING THE OAU-1 & 2, THE VRF CONDENSERS, AND THE |
| SMOKE CONTROL FANS AND FAN CURBS. |
| |
| 2) THE SUBMITTED NARRATIVE RESPONSE INDICATES |
| ADJUSTMENT OF VALUE BASED ON THE ELECTRICAL ONLY. |
| PLEASE INCLUDE THE VALUE INCREASE FOR MECHANICAL WHICH |
| INCLUDES THE CHANGE TO THE VRF SYSTEMS. |
| |
| 3) PLEASE INDICATE ON THE PLANS THAT ALL FIRE/SMOKE |
| DAMPERS AT SHAFT LOCATIONS WILL BE MOTORIZED TO OPERATE |
| AUTOMATICALLY IN SEQUENCE WITH THE SMOKE CONTROL |
| SYSTEM. PROVIDE AN "M" SYMBOL AT EACH LOCATION. |
| |
| 4) THE FOLLOWING IS A LIST OF DEFERRED SUBMITTALS FOR |
| THE MECHANICAL PERMIT THAT WILL REQUIRE SHOP DRAWING |
| APPROVAL BY THE ENGINEER OF RECORD. PLEASE NOTE THAT |
| WIND LOAD ENGINEERING FOR THE ROOFTOP UNITS MAY BE |
| ADDED TO THE LIST IF REQUESTED. |
| |
| A) SMOKE CONTROL FANS. |
| B) FIRE AND FIRE/SMOKE DAMPERS. |
| C) BAROMETRIC DAMPERS |
| D) DUCT SMOKE DETECTORS |
| E) AC ROOF AND DUCT STANDS, WALL BRACKETS |
| F) EXHAUST AND OUTSIDE AIR LOUVERS |
| G) PIPING INSULATIONS |
| H) ACCESS PANELS |
| I) GENERATOR |
| J) COMMERCIAL CLOTHES DRYERS |
| K) COOKING APPLIANCES |
| L) DUCT FIRE WRAPPING |
| M) FIRESTOPPING AND FIRE CAULKING |
| |
| 5) PLEASE SEE THE PROVISO NOTES UNDER THE MASTER PERMIT |
| #18020254. IT IS IMPORTANT THAT THESE REQUIREMENTS ARE |
| MET AS SOON AS POSSIBLE TO AVOID CONFLICTS IN THE |
| FIELD, AND TO AVOID DELAYS IN CONSTRUCTION, AND FOR CO |
| OF THE BUILDING. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |