Plan Review Notes
Plan Review Notes For Permit 18060457
Permit Number 18060457
Review Stop M
Sequence Number 1
Notes
Date Text
2018-06-26 11:24:191ST REVIEW FBC-2017 MECHANICAL
 REVISION #18060457
 MASTER #18020254
 6/26/18
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A REVISED ENERGY COMPLIANCE REPORT
 LISTING THE NEW VRF SYSTEMS- TABLE C403.2.3 (11) FBC
 EC.
  
 2) PROVIDE A REFRIGERANT PIPING RISER DRAWING FOR THE
 NEW SYSTEMS- SECTION 304.1 FBC M.
  
 3) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE
 NEW ROOF TOP CONDENSERS- SECTION 301.15 FBC M. SUBMIT A
 FL. PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE ROOF
 STANDS.
  
 4) SHEETS M-101, 102, & 103: SHOW THE REFRIGERANT
 PIPING RUNS AND CHASE LOCATIONS- SECTION 1107 FBC M.
  
 5) M-101, 102, 103: SHOW THE LOCATIONS OF ACCESS PANELS
 WHERE VRF UNITS ARE LOCATED ABOVE HARD CEILINGS. PLEASE
 INCLUDE NOTES AND DETAILS FOR CONSTRUCTION OF THE
 PANELS- SECTION 306.1 FBC M.
  
 6) M-102, 103: FIRE DAMPERS FOR O/A DUCTS PENETRATING
 THE CORRIDOR WALLS ARE SHOWN AT MANY LOCATIONS ON THE
 3RD- 9TH FLOORS (M-103), BUT ARE NOT SHOWN ON ANY OF
 THE PENETRATIONS ON THE 2ND FLOOR (M-102)- PLEASE
 CLARIFY.
  
 7) PROVIDE A UL APPROVED FIRESTOPPING ASSEMBLY FOR THE
 REFRIGERANT PIPE AND DUCT PENETRATIONS- SECTION 714 FBC
 B.
  
 8) PLEASE ADJUST THE 0.00 VALUE ON THE REVISION
 APPLICATION TO SHOW ALL ASSOCIATED COSTS WITH THE
 REDESIGN OF THE HVAC SYSTEMS INCLUDING, BUT NOT LIMITED
 TO A) LABOR, MATERIAL, EQUIPMENT TO INSTALL THE
 SYSTEMS. B) DEMOLITION, REMOVAL AND DISPOSAL OF THE
 COOLING TOWERS AND WATER PIPINGS, C) DESIGN FEES. SEE
 SECTION 109.3 WPB.
  
 9) PLEASE SEE THE PROVISO NOTES UNDER THE MASTER PERMIT
 #18020254. IT IS IMPORTANT THAT THESE REQUIREMENTS ARE
 MET AS SOON AS POSSIBLE TO AVOID CONFLICTS IN THE
 FIELD, AND TO AVOID DELAYS IN CONSTRUCTION, AND FOR CO
 OF THE BUILDING.
  
 10) THE FOLLOWING IS A LIST OF DEFERRED SUBMITTALS FOR
 THE MECHANICAL PERMIT THAT WILL REQUIRE SHOP DRAWING
 APPROVAL BY THE ENGINEER OF RECORD:
  
 A) SMOKE CONTROL FANS.
 B) FIRE AND FIRE/SMOKE DAMPERS.
 C) BAROMETRIC DAMPERS
 D) DUCT SMOKE DETECTORS
 E) AC ROOF AND DUCT STANDS, WALL BRACKETS
 F) EXHAUST AND OUTSIDE AIR LOUVERS
 G) PIPING INSULATIONS
 H) ACCESS PANELS
 I) GENERATOR
 J) COMMERCIAL CLOTHES DRYERS
 K) COOKING APPLIANCES
 L) DUCT FIRE WRAPPING
 M) FIRESTOPPING AND FIRE CAULKING
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER