Plan Review Notes For Permit 18060457 |
Permit Number |
18060457 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-26 18:38:14 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. VALUE FOR WORK STATED ON REVISION APPLICATION | | APPEARS LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE | | AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. | | FBC 109.3 | | 2. PLAN SHOWING NEW UNITS IS CALLING OUT CIRCUITS FROM | | PANELS THAT DON'T EXIST ON THE RISER DIAGRAM OR IN THE | | PANEL SCHEDULES. PROVIDE CORRECTIONS. NEC 215.2, 215.5, | | 408.4, 408.30; WPB FBC 107.2.1 | | 3. PROVIDE CORRECTED LOAD CALCULATIONS WITH NEW PANEL | | SCHEDULES. NEC 220 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|