2018-07-30 18:20:49 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| COMMENTS FROM PREVIOUS LIST: |
| |
| 1. FBC 109, VALUE IS TO INCLUDE ALL LABOR, MATERIALS, |
| OVERHEAD, PROFIT, INCLUDING MATERIALS PROVIDED BY |
| OTHERS. |
| |
| 2ND REVIEW, PROVIDE A COPY OF THE CONTRACT AND COST |
| BREAKDOWN. NO INFORMATION WAS PROVIDED, VALUE NOT |
| CHANGED. |
| |
| 2. PROFLEX MSC SPEC SHEET WAS PROVIDED. WE DO NOT HAVE |
| TEST REPORTS ON FILE FOR THIS PRODUCT, BUT WE DO FOR |
| PROFLEX RCU250, SUPERSIM90. EITHER SELECT AN ALTERNATE |
| PRODUCT OR PROVIDE THE FOLLOWING TEST REPORTS FOR |
| PROFLEX MSC: |
| |
| A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723. |
| |
| 2ND REVIEW, THE STC AND IIC TEST REPORTS INCLUDE A |
| DROPPED GYPSUM CEILING. |
| |