2018-06-15 06:50:47ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NEC 600.6A(1) DISCONNECT REQUIRED WITHIN SIGHT OF
 SIGN FOR 120V PRIMARY TO SIGN.
  
 2. PLAN STATES "PRIMARY ELECTRICAL TO SIGN PROVIDED BY
 OTHERS" WHO IS PERFORMING THE WORK? UNABLE TO ISSUE
 ELECTRICAL SUB-PERMIT TO CONTRACTOR. ELECTRICAL WORK
 REQUIRED OUT OF SCOPE OF LICENSE FOR (ES) SIGN
 CONTRACTORS SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN
 SPECIALTY CONTRACTOR) THE SCOPE OF CERTIFICATION
 INCLUDES THE STRUCTURAL FABRICATION INCLUDING CONCRETE
 FOUNDATION, ERECTION, INSTALLATION, ALTERATION, REPAIR,
 SERVICE AND WIRING OF ELECTRICAL SIGNS AND OUTLINE
 LIGHTING. THE SCOPE OF CERTIFICATION SHALL NOT INCLUDE
 THE PROVISION OF, OR ANY ELECTRICAL WORK BEYOND, THE
 LAST DISCONNECT MEAN OR TERMINAL POINTS. HOWEVER, A
 CONTRACTOR CERTIFIED UNDER THIS SECTION MAY PROVIDE THE
 ELECTRICAL ENTRANCE REQUIREMENTS FOR METERING AND MAIN
 DISCONNECT OF REMOTE BILLBOARDS OR SIGNS WHICH ARE
 INDEPENDENT OF ANY STRUCTURE OR BUILDING AND WHICH
 REQUIRE NO MORE THAN TWENTY-FIVE (25) KILOWATTS AT TWO
 HUNDRED FIFTY (250) VOLTS MAXIMUM. F.S. 489.505 (#19)
 AND F.A.C. 61G6-7.001
  
 3. VALUE TOO LOW, VALUE ADJUSTED TO 3000$. FBC 109.3
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECHURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 4. A PHYSICAL COPY OF AN ELECTRONICALLY OR DIGITALLY
 SIGNED, DATED AND SEALED DOCUMENT IS NOT A VALID
 SIGNED, DATED AND SEALED DOCUMENT. SIMILARLY, AN
 ELECTRONIC DOCUMENT (PDF, SCAN OR FAX COPY) OF A
 PHYSICALLY SIGNED, DATED AND SEALED DOCUMENT IS NOT A
 VALID SIGNED, DATED AND SEALED DOCUMENT. F.S.
 471/F.A.C. 61G15-23.004 (3)(C)(3)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved