2018-06-15 06:50:47 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. NEC 600.6A(1) DISCONNECT REQUIRED WITHIN SIGHT OF |
| SIGN FOR 120V PRIMARY TO SIGN. |
| |
| 2. PLAN STATES "PRIMARY ELECTRICAL TO SIGN PROVIDED BY |
| OTHERS" WHO IS PERFORMING THE WORK? UNABLE TO ISSUE |
| ELECTRICAL SUB-PERMIT TO CONTRACTOR. ELECTRICAL WORK |
| REQUIRED OUT OF SCOPE OF LICENSE FOR (ES) SIGN |
| CONTRACTORS SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN |
| SPECIALTY CONTRACTOR) THE SCOPE OF CERTIFICATION |
| INCLUDES THE STRUCTURAL FABRICATION INCLUDING CONCRETE |
| FOUNDATION, ERECTION, INSTALLATION, ALTERATION, REPAIR, |
| SERVICE AND WIRING OF ELECTRICAL SIGNS AND OUTLINE |
| LIGHTING. THE SCOPE OF CERTIFICATION SHALL NOT INCLUDE |
| THE PROVISION OF, OR ANY ELECTRICAL WORK BEYOND, THE |
| LAST DISCONNECT MEAN OR TERMINAL POINTS. HOWEVER, A |
| CONTRACTOR CERTIFIED UNDER THIS SECTION MAY PROVIDE THE |
| ELECTRICAL ENTRANCE REQUIREMENTS FOR METERING AND MAIN |
| DISCONNECT OF REMOTE BILLBOARDS OR SIGNS WHICH ARE |
| INDEPENDENT OF ANY STRUCTURE OR BUILDING AND WHICH |
| REQUIRE NO MORE THAN TWENTY-FIVE (25) KILOWATTS AT TWO |
| HUNDRED FIFTY (250) VOLTS MAXIMUM. F.S. 489.505 (#19) |
| AND F.A.C. 61G6-7.001 |
| |
| 3. VALUE TOO LOW, VALUE ADJUSTED TO 3000$. FBC 109.3 |
| BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE |
| WORK, ARCHITECHURAL AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| 4. A PHYSICAL COPY OF AN ELECTRONICALLY OR DIGITALLY |
| SIGNED, DATED AND SEALED DOCUMENT IS NOT A VALID |
| SIGNED, DATED AND SEALED DOCUMENT. SIMILARLY, AN |
| ELECTRONIC DOCUMENT (PDF, SCAN OR FAX COPY) OF A |
| PHYSICALLY SIGNED, DATED AND SEALED DOCUMENT IS NOT A |
| VALID SIGNED, DATED AND SEALED DOCUMENT. F.S. |
| 471/F.A.C. 61G15-23.004 (3)(C)(3) |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WPB |
| [email protected] |
| CELL: 561-657-1653 |
| |
| |