2018-06-20 16:10:301ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18060347
 6/20/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) REFER TO TABLE 403.3.1.1 FBC M: AN EXHAUST
 VENTILATION SYSTEM WITH A RATE OF 0.60 CFMS PER SQ. FT.
 IS REQUIRED FOR THE BEAUTY SALON. PLEASE NOTE THAT AIR
 FROM THE SALON SPACE CANNOT BE RECIRCULATED TO OTHER
 ROOMS AND SPACES PER FOOTNOTE B.
  
 2) SHEET M-1: REFER TO TABLE 403.3.1.1 FBC M AND
 CORRECT THE OUTDOOR AIR CALCULATIONS FOR THE PLAN- 25
 PERSONS PER 1000 SQ. FT. AT 20 CFMS PER PERSON + 0.12
 CFMS PER SQ. FT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  