2018-07-12 13:43:06 | BE ADVISED THAT A COURTESY REVIEW HAS BEEN PERFORMED |
| WITH THE DIGITAL PLANS THAT WERE EMAILED TO ME. |
| CORRECTIONS FOR COMMENTS BELOW SHOULD BE SUBMITTED WITH |
| PLANS THAT ARE DRAWN TO SCALE AND LEGIBLE, |
| SIGNED/SEALED BY THE DESIGN PROFESSIONAL RESPONSIBLE |
| FOR THE DESIGN. WPB FBC 107.1 |
| SEE BELOW FOR REVIEW: |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH |
| CODE. NEC 210.8, 215.5, 408.4 |
| 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| 250.50, 250.94, 408.30 |
| 3. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE |
| INCLUDING ALL LOADS. NEC 220 |
| 4. PROVIDE AIC RATING OF SERVICE EQUIPMENT AND PANELS. |
| NEC 110.3, 110.9 |
| 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 |
| 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| 7. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER |
| CODE. NEC 210.64 |
| 8. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH |
| SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE |
| MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC |
| MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS |
| OF FLORIDA STATUTES. PLANS SUBMITTED SHOULD MEET THIS |
| REQUIREMENT AND NEED TO BE LEGIBLE. WPB FBC 107.2.1.3, |
| 107.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |