Plan Review Notes
Plan Review Notes For Permit 18060308
Permit Number 18060308
Review Stop B
Sequence Number 3
Notes
Date Text
2018-12-12 11:09:14PROVISOS:
 ANY WORK INVOLVING POST TENSION SYSTEM MODIFICATIONS,
 OR IF TENDONS ARE DAMAGED WILL REQUIRE SPECIAL
 INPECTOR. THE SPECIAL INSPECTOR WILL NEED TO BE
 APPROVED ANDUTILIZED FOR NEW WORK OR REPAIRS.
  
 PROVIDE SUBMITTAL FOR FLOORING TO INCLUDE:
 1.IMPACT INSULATION CLASS (IIC) NOT LESS THAN 50, OR
 NOT LESS THAN 45 IF FIELD TESTED
 2. SOUND TRANSMISSION CLASS (STC) NOT LESS THAN 50, OR
 NOT LESS THAN 45 IF FIELD TESTED
 3. FLAME SPREAD INDEX AND SMOKE DEVELOPED INDEX
  
 SEPARATE PERMIT FOR FIRE ALARM WORK.
  