Plan Review Notes
Plan Review Notes For Permit 18060308
Permit Number 18060308
Review Stop P
Sequence Number 2
Notes
Date Text
2018-10-30 08:52:201ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A121 THE CLEAR FLOOR SPACE FOR THE SHOWER SHALL
 BE FLUSH WITH THE CONTROL WALL. PER FHA DESIGN MANUAL
 REQUIREMENT #7 PG. 7.56
 2. SHT. A121 IN THE CLEAR FLOOR SPACE FOR THE SHOWER
 THE LAVATORY SHALL BE ALLOWED TO OVERLAP THE CLEAR
 FLOOR SPACE ONLY 6? PLEASE CLARIFY THIS ON THE PLAN.
 PER FHA DESIGN MANUAL REQUIREMENT #7 PG. 7.57
 3. THE VANITY AND THE WING WALL NEXT TO THE VANITY
 SHALL HAVE A DEPTH NO MORE THAN 24?. PER FHA DESIGN
 MANUAL REQUIREMENT #7 PG. 7.44
 4. PLEASE LABEL ALL THE CLEAR FLOOR SPACE FOR THE
 PLUMBING FIXTURES IN THE BATHROOM WITH THE DIMENSIONS.
 PER FHA DESIGN MANUAL REQUIREMENT #7 PG. 7.43, 7.47,
 7.52, 7.56
 5. ALL BATHROOMS SHALL HAVE GRAB BAR BACKING PLEASE
 PROVIDE DETAIL DRAWINGS SHOWING THE LOCATION AND HEIGHT
 DIMENSIONS FOR THE GRAB BAR BACKING. PER FHA DESIGN
 MANUAL REQUIREMENT #6 PG. 6.3-6.13
 6. PLEASE CLARIFY WHAT TYPE OF SHOWER ENCLOSURE IS BE
 INSTALLED, UNDER THE PLUMBING FIXTURE SCHEDULE IT
 STATES AN ACRYLIC SHOWER STALL AND UNDER THE SPECS IT
 STATES A TILED SHOWER IF IT IS A TILED SHOWER PLEASE
 PROVIDE THE MANUFACTURE SPECIFICATIONS FOR THE SHOWER
 PAN WATER PROOFING. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  