2018-10-18 08:14:352ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18060308
 10/18/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE 16X8 TRANSFER GRILL FOR THE LARGE BEDROOM IS
 UNDERSIZED PER SECTION 601.6 FBC M (2)- 50 SQ. INCHES
 PER 100 CFMS REQUIRED FOR BALANCED AIR. IN ADDITION, IT
 APPEARS THAT THE AIR FROM THE BEDROOM THAT IS SUPPLIED
 BY HP-A WILL BE TRANSFERRED DIRECTLY INTO THE MAIN
 RETURN GRILL OF HP-B WHICH WILL CAUSE AN IMBALNCE IN
 THE SYSTEMS. A BETTER OPTION MAY BE TO DUCT THE RETURN
 DIRECTLY TO HP-B.
  
 2) THE NEW KITCHEN EXHAUST SHALL BE RUN INDEPENDENTLY
 OF THE TOILET ROOM EXHAUST, AND MUST MEET ALL THE
 COMPLIANCES LISTED UNDER SECTION 505.3 FBC M- SEE
 BELOW.
  
 505.3 COMMON EXHAUST SYSTEMS FOR DOMESTIC KITCHENS
 LOCATED IN MULTISTORY STRUCTURES.
  
 WHERE A COMMON MULTISTORY DUCT SYSTEM IS DESIGNED AND
 INSTALLED TO CONVEY EXHAUST FROM MULTIPLE DOMESTIC
 KITCHEN EXHAUST SYSTEMS, THE CONSTRUCTION OF THE SYSTEM
 SHALL BE IN ACCORDANCE WITH ALL OF THE FOLLOWING:
  
 1.THE SHAFT IN WHICH THE DUCT IS INSTALLED SHALL BE
 CONSTRUCTED AND FIRE-RESISTANCE RATED AS REQUIRED BY
 THE FLORIDA BUILDING CODE, BUILDING.
  
 2.DAMPERS SHALL BE PROHIBITED IN THE EXHAUST DUCT,
 EXCEPT AS SPECIFIED IN SECTION 505.1. PENETRATIONS OF
 THE SHAFT AND DUCTWORK SHALL BE PROTECTED IN ACCORDANCE
 WITH SECTION 607.5.5, EXCEPTION 2.
  
 3.RIGID METAL DUCTWORK SHALL BE INSTALLED WITHIN THE
 SHAFT TO CONVEY THE EXHAUST. THE DUCTWORK SHALL BE
 CONSTRUCTED OF SHEET STEEL HAVING A MINIMUM THICKNESS
 OF 0.0187 INCH (0.4712 MM) (NO. 26 GAGE) AND IN
 ACCORDANCE WITH SMACNA DUCT CONSTRUCTION STANDARDS.
  
 4.THE DUCTWORK WITHIN THE SHAFT SHALL BE DESIGNED AND
 INSTALLED WITHOUT OFFSETS.
  
 5.THE EXHAUST FAN MOTOR DESIGN SHALL BE IN ACCORDANCE
 WITH SECTION 503.2.
  
 6. THE EXHAUST FAN MOTOR SHALL BE LOCATED OUTSIDE OF
 THE AIRSTREAM.
  
 7.THE EXHAUST FAN SHALL RUN CONTINUOUSLY, AND SHALL BE
 CONNECTED TO A STANDBY POWER SOURCE.
  
 8. EXHAUST FAN OPERATION SHALL BE MONITORED IN AN
 APPROVED LOCATION AND SHALL INITIATE AN AUDIBLE OR
 VISUAL SIGNAL WHEN THE FAN IS NOT IN OPERATION.
  
 9.WHERE THE EXHAUST RATE FOR AN INDIVIDUAL KITCHEN
 EXCEEDS 400 CFM (0.19 M3/S) MAKEUP AIR SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 505.2.
  
 10.A CLEANOUT OPENING SHALL BE LOCATED AT THE BASE OF
 THE SHAFT TO PROVIDE ACCESS TO THE DUCT TO ALLOW FOR
 CLEANOUT AND INSPECTION. THE FINISHED OPENINGS SHALL BE
 NOT LESS THAN 12 INCHES BY 12 INCHES (305 MM BY 305
 MM).
  
 11.SCREENS SHALL NOT BE INSTALLED AT THE TERMINATION.
  
 12.THE COMMON MULTISTORY DUCT SYSTEM SHALL SERVE ONLY
 KITCHEN EXHAUST AND SHALL BE INDEPENDENT OF OTHER
 EXHAUST SYSTEMS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  