Plan Review Notes For Permit 18060308 |
Permit Number |
18060308 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-10-22 11:04:37 | PROVISOS: | | ANY WORK INVOLVING POST TENSION SYSTEM MODIFICATIONS, | | OR IF TENDONS ARE DAMAGED WILL REQUIRE SPECIAL | | INPECTOR. THE SPECIAL INSPECTOR WILL NEED TO BE | | APPROVED ANDUTILIZED FOR NEW WORK OR REPAIRS. | | | | COMMENT REVIEW NUMBER ONE SUGGESTED THAT SEPARATE | | PERMIT BE APPLIED FOR EACH UNIT. THIS WAS NOT DONE, SO | | ALL UNITS WILL BE UNDER ONE PERMIT. WORK WILL NEED TO | | BE DONE AS ONE PROJECT. | | | | PROVIDE SUBMITTAL FOR FLOORING TO INCLUDE: | | 1.IMPACT INSULATION CLASS (IIC) NOT LESS THAN 50, OR | | NOT LESS THAN 45 IF FIELD TESTED | | 2. SOUND TRANSMISSION CLASS (STC) NOT LESS THAN 50, OR | | NOT LESS THAN 45 IF FIELD TESTED | | 3. FLAME SPREAD INDEX AND SMOKE DEVELOPED INDEX | | | | SEPARATE PERMIT FOR FIRE ALARM WORK. | | |
|