2018-07-11 18:06:59 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18060308 |
| 7/11/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M-121: PROVIDE A MEANS OF RETURNING AIR FROM |
| THE BEDROOMS- SECTION 601.6 FBC M. |
| |
| 2) M-121: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| NEW COOKING APPLIANCE- SECTION 917.1 FBC M. |
| |
| 3) M-121: EXHAUST VENTILATION IS REQUIRED FOR THE |
| KITCHEN AT A RATE OF 25 CFMS CONTINUOUS, OR 100 CFMS |
| INTERMITTENTLY PER TABLE 403.3.1.1 FBC M. INDICATE IF A |
| NEW KITCHEN EXHAUST HOOD AND EXHAUST DUCT ARE TO BE |
| INSTALLED AND: A) SUBMIT MANUFACTURER'S SPECIFICATIONS |
| FOR THE SYSTEM. B) PROVIDE A DETAIL SHOWING THE EXHAUST |
| DUCT RUN AND TERMINATION LOCATION- SECTION 505 FBC M |
| |
| 4) CLARIFY IF A NEW OR RELOCATED DRYER IS TO BE |
| INSTALLED AND: A) SUBMIT MANUFACTURER'S SPECIFICATIONS. |
| B) SHOW THE LOCATION OF THE DRYER AND THE EXHAUST DUCT |
| RUN AND TERMINATION LOCATION.- SECTION 504 FBC M. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |