2018-07-11 18:06:591ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18060308
 7/11/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-121: PROVIDE A MEANS OF RETURNING AIR FROM
 THE BEDROOMS- SECTION 601.6 FBC M.
  
 2) M-121: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 NEW COOKING APPLIANCE- SECTION 917.1 FBC M.
  
 3) M-121: EXHAUST VENTILATION IS REQUIRED FOR THE
 KITCHEN AT A RATE OF 25 CFMS CONTINUOUS, OR 100 CFMS
 INTERMITTENTLY PER TABLE 403.3.1.1 FBC M. INDICATE IF A
 NEW KITCHEN EXHAUST HOOD AND EXHAUST DUCT ARE TO BE
 INSTALLED AND: A) SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE SYSTEM. B) PROVIDE A DETAIL SHOWING THE EXHAUST
 DUCT RUN AND TERMINATION LOCATION- SECTION 505 FBC M
  
 4) CLARIFY IF A NEW OR RELOCATED DRYER IS TO BE
 INSTALLED AND: A) SUBMIT MANUFACTURER'S SPECIFICATIONS.
 B) SHOW THE LOCATION OF THE DRYER AND THE EXHAUST DUCT
 RUN AND TERMINATION LOCATION.- SECTION 504 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  