2018-07-23 11:00:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE G2 ON SHEET E-001 AND SHEET G-100 SPECIFY THE
 WRONG CODE FOR DESIGN. THESE ARE IN CONFLICT WITH OTHER
 AREAS OF THE PLAN THAT STATE THE CURRENT CODE. CORRECT
 DISCREPANCIES. WPB FBC 107.2.1; FBC PREFACE
 2. DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE. PROVIDE
 CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
 3. BE ADVISED THAT FIRE ALARM IS NOT INCLUDED IN THE
 SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR THIS. WPB FBC 105.1, 107.2.1
 4. SHEET E-002 HAS A NOTE FOR PATIENT CARE AREAS, BUT
 REVIEWER DOES NOT SEE ANY PATIENT CARE AREAS IDENTIFIED
 ON PLAN. PROVIDE CLARIFICATION AND/OR CORRECTION. WPB
 FBC 107.2.1
 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL TO CONFIRM THE STATED AIC RATING OF THE PANELS IS
 ADEQUATE. NEC 110.9, 110.10
 6. NOTE ON PANEL SCHEDULE INDICATES THAT ALL BREAKERS
 SHALL BE AFCI TYPE. BRANCH CIRCUITS THAT FEED EQUIPMENT
 SUCH AS A RANGE OR AN AC ARE NOT TYPICALLY INSTALLED
 WITH AFCI PROTECTION. PROVIDE CLARIFICATION AS TO WHICH
 CIRCUITS ARE AFCI PROTECTED PER CODE. NEC 210.12
 7. PLAN SHOWS WHAT APPEARS TO BE A STANDARD RECESS
 LIGHT OVER SHOWER. LIGHTING IN BATHTUB OR SHOWER AREAS
 SHALL BE SUITABLE FOR DAMP LOCATIONS. PROVIDE
 CORRECTION. NEC 410.10(D)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  