Plan Review Notes
Plan Review Notes For Permit 18060308
Permit Number 18060308
Review Stop B
Sequence Number 1
Notes
Date Text
2018-07-26 16:43:24BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS
  
 1- THE PROPOSED WORK INVOLVES 3 SEPARATE FLOORS.
 PROVIDE A SEPARATE PERMIT APPLICATION FOR EACH FLOOR.
 CLEARLY IDENTIFY THE UNIT OF EACH WHERE ALTERATION IS
 GOING TO TAKE PLACE. NOTE: SAME PLANS MAY BE USED, BUT
 NEED A SEPARATE PERMIT APPLICATION FOR EACH UNIT FOR
 PROPER INSPECTIONS. SEC. 105.1 CITY AMENDMENTS.
  
 2- THIS IS A THRESHOLD BUILDING. SPECIAL INSPECTOR MAY
 BE REQUIRED FOR NEW FLOOR PENETRATIONS INTO EXISTING
 POST TENSIONED SLAB. LOCATION OF PT TENDONS AND
 REINFORCEMENT IN SLAB IS REQUIRED BEFORE CORE DRILLING.
 COORDINATE WITH KEN CONRAD (CHIEF BUILDING INSPECTOR)
 PRIOR TO ANY WORK. SEE CONTACT INFORMATION BELOW.
  
 KEN CONRAD
 CHIEF BUILDING INSPECTOR
 PHONE: 805-6666 EXT: 6666
 E-MAIL: [email protected]
  
 3- -SHEET A-121-NEW PLAN:
 A)IT LOOKS LIKE THE SLIDING DOORS FOR CLOSET IN
 SECONDARY BEDROOM DON'T COMPLY WITH THE 32" USABLE
 DOORS REQUIREMENT #3 OF FAIR HOUSING ACT. SEE PAGE 3.9
 AND PAGE 3.14 OF FAIR HOUSING ACT MANUAL. REVISE AS
 REQUIRED.
  
 B)PURPLE DASHED LINES SHOWN ON KITCHEN AND BATHROOMS
 USED TO ILLUSTRATE THE CLEAR FLOOR SPACE BY THE
 APPLIANCES ARE NOT CLEAR. CLEARLY SHOW THE CLEAR FLOOR
 SPACE IN FRONT OF EACH APPLIANCE. NOTE: CLEARLY SPECIFY
 IF THERE ARE CABINETS BELOW PLUMBING FIXTURES.
 COORDINATE WITH SHEET A-460. THE KITCHEN ISLAND HAVE
 CABINETS BELOW, THEREFORE,THERE IS NO KNEE SPACE BELOW
 THE COUNTER. CLEARLY SHOW THE CLEAR DIMENSION BETWEEN
 THE REFRIGERATOR AND THE KITCHEN ISLAND. SEE PAGE 7.6
 AND 7.7 OF FAIR HOUSING ACT MANUAL.
  
 C) CLEARLY IDENTIFY WHICH TYPE OF BATHROOMS TO BE USED.
 "A" OR "B". SEE PAGE 7.34 OF FAIR HOUSING ACT MANUAL
 FOR PROPER REVIEW COMPLIANCE. NOTE: IT LOOKS LIKE THERE
 MAY BE AN ISSUE WITH THE DOOR IN WATER CLOSET
 COMPARTMENT OF BATHROOM LOCATED IN THE MIDDLE OF THE
 APARTMENT. IT LOOKS LIKE THERE MAY BE CONFLICT WITH THE
 REQUIRED CLEAR FLOOR SPACE OUTSIDE THE SWING OF THE
 DOOR.
  
  
 D) IT LOOKS LIKE THE SHOWERS DON'T COMPLY WITH THE
 CLEAR FLOOR SPACE THAT NEEDS TO BE PARALLEL AND FLUSHED
 WITH THE CONTROL WALL. SEE PAGE 7.56 OF FAIR HOUSING
 ACT MANUAL. REVISE AS REQUIRED.
  
 4--SHEET G-100:
 A)REVISE PROJECT CODE ANALYSIS (SEC. 107.2.1 CITY
 AMENDMENTS):
 (1)PROVIDE CORRECT FLOORS TO MATCH PERMIT APPLICATION
 AND PLANS. WORK IS ON FLOORS 10 THRU 12 NOT 8 THRU 10.
 (NOTE: ALSO NEED A PERMIT APPLICATION FOR EACH FLOOR
 UNIT)
 (2)REVISE JURISDICTION CONTACT INFORMATION. CURRENT
 BUILDING OFFICIAL IS ROBERT BROWN NOT DOUG WISE. REVISE
 PHONE NUMBER AND E-MAIL AS WELL. NOTE: THIS IS NOT PALM
 BEACH COUNTY JURISDICTION. THIS IS THE CITY OF WEST
 PALM BEACH. PHONE NUMBER AND E-MAIL ADDRESS IS NOT
 REQUIRED.
  
 B) THE CURRENT CODE IS THE FBC, 6TH EDITION (2017)
 UPDATE ALL THE INFORMATION ON SHEET G-100 THAT IS
 REFERENCING THE 2014 CODE.
 CHAPTER 553 F.S.
  
 C) REVISE/CLARIFY BUILDING DATA. ACCORDING TO CITY
 RECORDS (PERMIT #95009927) 3RD AND 4TH FLOORS HAVE HAVE
 NURSING UNITS, 5TH AND 6TH FLOORS HAVE ASSISTED LIVING
 UNITS AND 8TH THRU 11TH FLOOR AND PENTHOUSE HAVE
 INDEPENDENT UNITS. FOR CLARIFICATION THE OCCUPANCY OF
 THIS BUILDING IS A MIXED USE OF NURSING HOME, ASSISTED
 LIVING FACILITY AND INDEPENDENT LIVING FACILITY FOR THE
 ELDERLY. UNITS ON FLOORS 10 THRU 12 ARE RESIDENTIAL
 (R2).
 SEC. 301.1 FBC.
  
 5- FLOORING UNDERLAYMENT SOUND INSULATION MATERIAL TO
 BE USED FOR CERAMIC TILE AND WOOD FLOORING(NOTE: THIS
 MAY BE SUBMITTED LATER AS A DEFERRED SUBMITTAL.
 DESIGNER OF RECORD TO APPROVE THEM BEFORE SUBMITTAL):
 A) PROVIDE COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
 NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION.
  
 B) PROVIDE COPIES OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 6TH EDITION (2017).
 NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE
 ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING.
  
 C) PROVIDE COPIES OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 6TH EDITION (2017).
 NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE
 ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING.
  
 6- SHEET A-460-FINISH PLAN + ELEVATIONS + DETAILS:
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 REINFORCEMENT AT ALL THE GRAB BARS AS REQUIRED BY
 REQUIREMENT #6 OF FAIR HOUSING ACT. NOTE: REMEMBER TYPE
 OF CONSTRUCTION. COMBUSTIBLE MATERIALS ARE NOT ALLOWED.
 SEE SEC. 603.1 FBC FOR PERMITTED MATERIALS.
  
 7- SHEET G-201 -EXISTING LIFE SAFETY PLANS:
 A) REVISE THE EXIT ACCESS TRAVEL DISTANCE. THE DISTANCE
 IS MEASURE FORM THE MOST REMOTE POINT TO THE EXIT NOT
 TO THE ENTRY DOOR. SEE SEC. 1017.3 FBC AND REVISE AS
 REQUIRED.
  
 B)EXISTING LIFE SAFETY PLANS SHOW A FIRE EXTINGUISHER
 WHERE THE NEW CORRIDOR WALL IS BUILT FOR NEW APARTMENT.
 SPECIFY LOCATION OF RELOCATED FIRE EXTINGUISHER. SEC.
 906.1 FBC.
  
 8- SHEET G-500-UL ASSEMBLIES: PROVIDE SPECIFICATIONS
 FOR RATED CEILING ASSEMBLY. SEC. 420.3 FBC
  
 9- SHEET FP-001-GENERAL INFORMATION-FIRE PROTECTION:
 REVISE INFORMATION SPECIFIED UNDER RESIDENTIAL UNITS IN
 THE FIRE PROTECTION DESIGN CRITERIA COLUMN. THIS
 BUILDING REQUIRES A NFPA 13 SPRINKLER SYSTEM. SEC.
 903.3.2 FBC. NFPA 13R SPRINKLER SYSTEM IS NOT ALLOWED.
 NFPA 13R SYSTEM IS FOR LOW RISE RESIDENTIAL
 OCCUPANCIES. REVISE AS REQUIRED.
 SEPARATE PERMIT REQUIRED.
  
 10- PROVIDE SPECIFICATIONS FOR FIRE ALARM AND SMOKE
 ALARMS. SEC. 907.2.9 FBC.
 SEPARATE PERMIT REQUIRED.
  
 11- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 PENETRATIONS IF FIRE RATED HORIZONTAL ASSEMBLIES AND
 FIRE RATED WALLS.
 SEC. 714 FBC.
  
 12- THIS IS A DIGITAL SUBMITTAL. ALL DRAWINGS NEED TO
 HAVE DIGITAL SIGNATURE AS REQUIRED BY CHAPTER 481 FOR
 ARCHITECTS AND CHAPTER 471 FOR ENGINEERS.
  
 13- PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]