Plan Review Notes For Permit 18060285 |
Permit Number |
18060285 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-20 14:33:06 | PASSED WITH THE FOLLOWING PROVISO: | | | | 1. ENSURE THAT NOTIFICATION APPLIANCES ARE CREATING | | 75DB AT THE PILLOW TOP OF EACH BEDROOM IN ACCORDANCE | | WITH NFPA 72 ? 7.4.4.1 | | | | 2. ENSURE THAT ALL EXTERNAL DEVICES ARE EQUIPPED WITH | | WEATHER PROOF ENCLOSURES. | | | | 3. TEST ALL EXISTING DEVICES TO ENSURE COMPATIBILITY | | AND FUNCTIONALITY WITH NEW FIRE ALARM COMMUNICATOR. | | | | 4. ENSURE THAT ALL FIRE ALARM PULL STATIONS ARE | | INSTALLED TO MEET NFPA 72 INCLUDING HEIGHT AND TRAVEL | | DISTANCES. | | | | 5. PROVIDE RECORD OF COMPLETION AT TIME OF INSPECTION. | | | | 6. ANY DETECTION DEVICES EXPOSED TO THE ELEMENTS SHALL | | BE HEAT DETECTION AS OPPOSE TO SMOKE DETECTION TO | | ALLEVIATE FALSE ALARMS. | | | | |
|