2019-03-01 09:34:10PROVISO 18060261
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE A BACKFLOW ON THE ICEMAKERS, WATER FILTERS
 AND COFFEE MAKERS. PER FBC PL 608.3, 608.16.10
 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
 3. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTORS
 APPROVAL.
 4. ALL PLUMBING WORK SHALL COMPLY WITH FBC PLUMBING 6TH
 EDITION 2017
 5. TRAP PRIMER REQUIRED ON THE FLOOR DRAIN. PER FBC PL
 1002.4.1
 6. THE NEW SINK DRAIN PIPING SHALL CONNECT TO BUILDING
 BRANCH DRAIN DOWN STREAM OF THE EXISTING BATHROOM
 GROUP. PER FBC PL 912.1
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]