2018-06-13 10:53:09PERMIT # 18060261
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO:
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) SHEET FAC1-04-1: PROPER COORDINATION OF EXITSTING
 AND NEW FIRE ALARM SYSTEMS NEEDED TO ENSURE THAT THE
 INTEGRITY OF THE EXISTING FIRE ALARM SYSTEM IS
 MAINTAINED THROUGHOUT TO ENSURE THAT THE FULL BUILDING
 HAS PROPER FIRE ALARM COVERAGE AT ALL TIMES, UNTIL SUCH
 TIME AS BOTH SYSTEMS ARE COMBINED INTO ONE.
  
 3) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
  